5-192 G60 Generator Management Relay GE Multilin5.7 INPUTS/OUTPUTS 5 SETTINGS5c) TELEPROTECTION OUTPUTSPATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ TELEPROTECTION ÖØ TELEPROT OUTPUTSAs the following figure demonstrates, processing of the teleprotection inputs/outputs is dependent on the number of com-munication channels and terminals. On two-terminal two-channel systems, they are processed continuously on each chan-nel and mapped separately per channel. Therefore, to achieve redundancy, the user must assign the same operand onboth channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). Onthree-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channelfailure between any pair of relays.Figure 5–114: TELEPROTECTION INPUT/OUTPUT PROCESSING TELEPROT OUTPUTSTELEPROT OUTPUT 1-1:OffRange: FlexLogic™ operandMESSAGE TELEPROT OUTPUT 1-2:OffRange: FlexLogic™ operand↓MESSAGE TELEPROT OUTPUT 1-16:OffRange: FlexLogic™ operandMESSAGE TELEPROT OUTPUT 2-1:OffRange: FlexLogic™ operandMESSAGE TELEPROT OUTPUT 2-2:OffRange: FlexLogic™ operand↓MESSAGE TELEPROT OUTPUT 2-16:OffRange: FlexLogic™ operand842750A2.CDRTELEPROT OUTPUT 1-1:(same for 1-2...1-16)TELEPROT INPUT 1-1DEFAULT:(same for 1-2...1-16)Off (Flexlogic Operand)TELEPRO INPUT 1-1 On(same for 1-2...1-16)UR-1(Teleprotection I/O Enabled)Communication channel #1OnOffACTUAL VALUESCHANNEL 1 STATUS:FailOKORSETTINGTELEPROT OUTPUT 1-1:TELEPROT OUTPUT 2-1:(same for 1-2...1-16)Off (Flexlogic Operand)FLEXLOGIC OPERANDTELEPRO INPUT 1-1 OnTELEPRO INPUT 2-1 On(same for 1-2...1-16)UR-2SETTINGSETTINGTELEPROT INPUT 1-1TELEPROT INPUT 2-1DEFAULT:(same for 1-2...1-16)OnOffFailOK ORACTUAL VALUESACTUAL VALUESCHANNEL 1 STATUS:(On 3-terminal system or 2-terminalwith redundant channel)Communication channel #2OnOffACTUAL VALUESCHANNEL 2 STATUS:FailOKORSETTING(same for 2-2...2-16)Off (Flexlogic Operand)FLEXLOGIC OPERAND(same for 2-2...2-16)DEFAULT:(same for 2-2...2-16)OnOffFailOK ORCHANNEL 2 STATUS:UR-2 or UR-3SETTINGSETTINGFLEXLOGIC OPERANDTELEPROT OUTPUT 2-1:(same for 1-2...1-16)TELEPROT INPUT 2-1DEFAULT:(same for 1-2...1-16)Off (Flexlogic Operand)TELEPRO INPUT 2-1 On(same for 1-2...1-16)SETTINGSETTINGFLEXLOGIC OPERAND