5-60 M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5Buffered Report1 TrgOpsRange: The check box for an individual bit can be enabled or notDefault: All bits trueThe TrgOps setting is bitstring that controls which trigger conditions are monitored in this report. The options are asfollows:– data-change– quality-change– integrity– general interrogationBuffered Report1 IntgPdRange: 0 to 4294967295 in steps of 1Default: 0The entered value sets the period in milliseconds for generating Buffered Report1 integrity reports. An integrity reportincludes the values of all members of the referenced data set, whether a change has occurred or not.Each unbuffered report has the following settings.Unbuffered Report1 RptIDRange: 0 to 129 VisibleString charactersDefault:The entered value sets the RptID value in Unbuffered Report1 messages, and it can be used by the client to discriminateUnbuffered Report1 messages from other messages. If the number of characters entered is zero, the value used forRptID in messages is an ObjectReference to the report's control block, that is, "/LLN0$RP$"URCB01".Unbuffered Report1 DatSetRange: None, DataSet01, DataSet02, …Default: NoneThis setting selects the data set whose members' status is reported in Unbuffered Report1 messages using the UR Setupsoftware designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, asdescribed later.An ObjectReference to the data set, which consists of the concatenation of the string "/LLN0$" and the dataset name, is used in the datSet field of report messages, and it can be used by the client to discriminate UnbufferedReport1 messages from other messages.Unbuffered Report1 ConfRevRange: 0 to 4294967295 in steps of 1Default: 0The entered value sets the confRev value in Unbuffered Report1 messages, and it can be used by clients to discriminatereport messages of the expected configuration revision from messages of a different revision. The standard requiresthat confRef be incremented each time the members or the order of the members is changed, and each time the dataset name is changed.Unbuffered Report1 OptFldsRange: The check box for an individual bit can be enabled or notDefault: All bits trueThe OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The options areas follows:– sequence-number– report-time-stamp– reason-for-inclusion– data-set-name– data-reference