CHAPTER 5: SETTINGS GROUPED ELEMENTSM60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-2295Figure 5-126: Auxiliary undervoltage logic5.7.10.7 Auxiliary overvoltage (ANSI 59X, IEC PTOV)SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) VOLTAGE ELEMENTS AUXILIARY OV1(2)The M60 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltageconditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEMSETUP AC INPUTS VOLTAGE BANK X5 AUXILIARY VT X5 SECONDARY is the per-unit (pu) base used when setting thepickup level.A typical application for this element is monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-deltaVT connection. AUXILIARY OV1 AUX OV1FUNCTION: DisabledRange: Disabled, Enabled AUX OV1 SIGNALSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4 AUX OV1 PICKUP:0.300 puRange: 0.000 to 3.000 pu in steps of 0.001 AUX OV1 PICKUPDELAY: 1.00 sRange: 0.00 to 600.00 s in steps of 0.01 AUX OV1 RESETDELAY: 1.00 sRange: 0.00 to 600.00 s in steps of 0.01 AUX OV1 BLOCK:OffRange: FlexLogic operand AUX OV1 TARGET:Self-resetRange: Self-reset, Latched, Disabled AUX OV1 EVENTS:DisabledRange: Disabled, Enabled827849A3.CDRFLEXLOGIC OPERANDSAUX UV1FUNCTION:AUX UV1 BLOCK:AUX UV1 SIGNALSOURCE:AUX UV1 MINIMUMVOLTAGE:AUX UV1 DPOAUX UV1 OPAUX UV1 PKPRUNSETTINGSETTINGAUX UV1 CURVE:AUX UV1 DELAY:AUX UV1 PICKUP:SETTINGEnabled=1SETTINGSETTINGOff=0AUX VOLT Vx Vx MinimumVx PickuptV<<AND