CHAPTER 5: SETTINGS PRODUCT SETUPM60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-9355.3.10.3 Trip and alarm LEDsSETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS TRIP & ALARMS LEDSThe trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Eachindicator can be programmed to become illuminated when the selected FlexLogic operand is in the logic 1 state.5.3.10.4 User-programmable LED 1(48)SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LED 1(48)There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illuminatewhen the selected FlexLogic operand is in the logic 1 state.For the standard faceplate, the LEDs are located as follows:• LED Panel 2 — User-programmable LEDs 1 through 24• LED Panel 3 — User programmable LEDs 25 through 48For the enhanced faceplate, the LEDs are located as follows:• LED column 2 — User-programmable LEDs 1 through 12• LED column 3 — User-programmable LEDs 13 through 24• LED column 4 — User-programmable LEDs 25 through 36• LED column 5 — User-programmable LEDs 37 through 48See the LED Indicators section in chapter 4 for information on the location of these indexed LEDs.The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the LED 1 TYPE setting is “Self-Reset” (the default setting), the LED illumination tracks the state of the selected LED operand. If the LED 1 TYPE setting is“Latched,” the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via acommunications channel, or from any programmed operand, even if the LED operand state de-asserts.Table 5-13: Recommended settings for user-programmable LEDs TRIP & ALARM LEDS TRIP LED INPUT:OffRange: FlexLogic operand ALARM LED INPUT:OffRange: FlexLogic operand USER-PROGRAMMABLE LED 1 LED 1 OPERAND:OffRange: FlexLogic operand LED 1 TYPE:Self-ResetRange: Self-Reset, LatchedSetting Parameter Setting ParameterLED 1 operand SETTING GROUP ACT 1 LED 13 operand OffLED 2 operand SETTING GROUP ACT 2 LED 14 operand OffLED 3 operand SETTING GROUP ACT 3 LED 15 operand OffLED 4 operand SETTING GROUP ACT 4 LED 16 operand OffLED 5 operand SETTING GROUP ACT 5 LED 17 operand OffLED 6 operand SETTING GROUP ACT 6 LED 18 operand OffLED 7 operand Off LED 19 operand OffLED 8 operand Off LED 20 operand OffLED 9 operand Off LED 21 operand OffLED 10 operand Off LED 22 operand OffLED 11 operand Off LED 23 operand OffLED 12 operand Off LED 24 operand Off