Appendix D. Product Certifications and Standards310 PACSystems* RXi Distributed IO Controller User Manual GFK-2816FD.2 Standards OverviewFor environmental specifications, refer to Section 1.1.3, RXi Controller EnvironmentalSpecifications.EMC Emissions and Immunity SpecificationsEMC Product StandardsIndustrial ControlEquipmentEN 61131-2 EMC Zone B requirementsInformation TechnologyEquipmentEN 55022EN 55024EmissionsImmunityGeneric Standards EN 61000-6-2EN 61000-6-4ImmunityEmissionsEMC EMISSIONSEmissions CISPR 11/EN 55011/EN55016-2-330 – 1000 MHz, radiated, Group 1, Class A,FCC 47CFR15 30 – 7500 MHz, radiated, Class ACISPR 22/EN55022 30 – 6000 MHz, radiated, Class A,Ethernet port: 0.15 – 30 MHz, conducted, Class AEMC IMMUNITYElectrostatic Discharge EN61000-4-220 8.0 kV air, 4.0 kV contact,RF Susceptibility EN 61000-4-320 1kHz sine wave, 80% AM10 V/m, 80 – 1000 MHz3 V/m, 1.0 – 2.0 GHz1 V/m, 2.0 – 2.7 GHzFast Transient EN 61000-4-420 DC Input: 2 kV, 33 nF directEthernet port, shielded:1.1 kV, capacitive clampRS-232 port, unshielded:1.1 kV, capacitive clampSurge EN 61000-4-520 DC Input: 0.5 kV, 12 ohms (CM); 0.5 kV,2 ohms (DM)Ethernet port, shielded: ±1.0 kV, 2 ohms (CM)Conducted RF Immunity EN 61000-4-620 DC Input: 10 V, CDNEthernet port, shielded: 10 V, current clampRS-232 port, unshielded: 10 V, current clampDamped Oscillatory Wave EN 61000-4-1820 DC Input: 2. 5kV, 1 MHz (CM/DM);Ethernet port, shielded: 2.5 kV, 1 MHz (CM)RS-232 port, unshielded: 2.5 kV, 1 MHz (CM)Product SafetyOrdinary Locations:UL/CSA/EN/IEC 60950-1 Requires: LPS or Class 2 power source, Pollution Degree 2 environmentUL508, CSA 22.2 No 142 Requires: LPS, Class 2, or LVLC power source, Pollution Degree 2environment20 EN 61000-4-x series of tests are technically equivalent to the IEC 61000-4-x series.