6–12 PQMII POWER QUALITY METER – INSTRUCTION MANUALCHAPTER 6: MONITORING• 3Φ/AΦ/BΦ/CΦ kVA MIN/MAX: The minimum/maximum three phase apparent poweras well as the minimum/maximum individual phase A/B/C apparent power isdisplayed, along with the time and date of their measurement. This information isstored in non-volatile memory and will be retained during a loss of control power. Thephase A/B/C minimum/maximum apparent power messages will be displayed only fora “Wye” connected system.• 3Φ/AΦ/BΦ/CΦ PF MIN/MAX: The minimum/maximum three phase lead or lag powerfactor as well as the minimum/maximum lead or lag individual phase A/B/C powerfactor is displayed, along with the time and date of their measurement. Thisinformation is stored in non-volatile memory and will be retained during a loss ofcontrol power. The phase A/B/C minimum/maximum lead or lag power factormessages will be displayed only for a “Wye” connected system.FIGURE 6–1: Power Measurement Conventions6.2.5 Energy MeteringPATH: ACTUAL VALUES Ö A1 METERING ÖØ ENERGYPQMII ENERGY [Z] 3Φ POS REAL ENERGY= 32745 kWh