5–6 PQMII POWER QUALITY METER – INSTRUCTION MANUALCHAPTER 5: SETPOINTS5.2.3 Setpoint AccessPATH: SETPOINTS Ö S1 PQMII SETUP ÖØ SETPOINT ACCESSTo enable setpoint access, follow the steps outlined in the following diagram:The factory default access code for the PQMII is 1.If three attempts are made to enable setpoint access with an incorrect code, the value ofthe setpoint access setpoint changes to “Disabled” and the above procedure must berepeated.Once setpoint access is enabled, the Program LED indicator turns on. Setpoint alterationsare allowed as long as the Program LED indicator remains on. Setpoint access is bedisabled and the Program LED indicator turns off when:• The time programmed in S1 PQMII SETUP Ö SETPOINT ACCESS ÖØ SETPOINT ACCESS ON FORis reached• The control power to the PQMII is removed• The factory setpoints are reloadedTo permanently enable the setpoint access feature, enable setpoint access and then setSETPOINT ACCESS ON FOR to “Unlimited”. Setpoint access remains enabled even if the controlpower is removed from the PQMII. SETPOINT [Z]ACCESSSETPOINT ACCESS:DISABLERange: Disable, EnableMESSAGE ENTER SETPOINTACCESS CODE: 1Range: 1 to 999 in steps of 1MESSAGE SETPOINT ACCESS ONFOR: 5 min.Range: 1 to 300 min. in steps of 1 orUnlimitedMESSAGE CHANGE SETPOINTACCESS CODE: NoRange: No, YesMESSAGE ENTER NEW ACCESSCODE: 0Range: 1 to 999 in steps of 1MESSAGE RE-ENTER NEW ACCESSCODE: 0Range: 1 to 999 in steps of 1MESSAGE ENCRYPTED SETPOINTACCESS CODE: 376Range: N/ASETPOINT ACCESS:ENABLEENTER SETPOINTACCESS CODE: 1SETPOINT ACCESS ONFOR: 5 min.SETACCEN.CDRINCORRECT CODECORRECTCODEINCORRECTCODESTORE STOREENTER ENTER