5-54 C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5Figure 5-15: RxGOOSE Boolean panelRxGOOSE Boolean1 IDRange: 0 to 12 charactersDefault: RxG Bool1This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The fulloperand name is the value of this setting appended with " On". This descriptive text also appears in the SCL filesassociated with the UR.RxGOOSE Boolean1 RxGOOSERange: None, RxGOOSE1, RxGOOSE2, and so onDefault: NoneThis setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set toNone, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.RxGOOSE Boolean1 MemberRange: 1 to 64 in steps of 1Default: 1This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1selects the first member, 2 selects the second member, and so on. Entering a number greater than the number ofmembers in the message and entering the number of a member that is not a BOOLEAN results in the RxGOOSEBoolean1 FlexLogic operand assuming its default state.RxGOOSE Boolean1 DEFAULT STATERange: On, Off, Latest/On, Latest/OffDefault: OnThis setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup andthe selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with thepublisher. The following choices are available:– "On" value defaults the input to logic 1– "Off" value defaults the input to logic 0– "Latest/On" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-upbut before the first communication, the input defaults to logic 1. When communication resumes, the inputbecomes fully operational.– "Latest/Off" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-upbut before the first communication, the input defaults to logic 0. When communication resumes, the inputbecomes fully operational.