CHAPTER 4: INTERFACES ENERVISTA SOFTWARE INTERFACEC60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL 4-344. Site list / online window area5. Settings list / offline window area6. Software windows, with common tool bar7. Settings file data view windows, with common tool bar8. Workspace area with data view tabs9. Status bar10. Quick action hot linksFigure 4-1: EnerVista UR Setup software window4.1.6 Settings templatesSettings file templates simplify the configuration and commissioning of multiple relays that protect similar assets. Anexample is a substation that has 10 similar feeders protected by 10 UR-series F60 relays.In these situations, typically 90% or greater of the settings are identical among devices. The templates feature allowsengineers to configure and test these common settings, then lock them so that they are not available to users. Forexample, these locked down settings can be hidden from view for field engineers, allowing them to quickly identify andconcentrate on specific settings.The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineersinstalling the devices. These are settings such as protection element pickup values and CT and VT ratios.The settings template mode allows the user to define which settings are visible in the EnerVista software. Settingstemplates can be applied to both settings files (settings file templates) and online devices (online settings templates). Thefunctionality is identical for both purposes.Settings files conversion from previous firmware versions is supported.123456 789 842786A2.CDR10