Appendix B. Environmental SpecificationsUnless otherwise noted on individual specification pages, the followingenvironmental specifications, based on an altitude from sea level to 2134 meters(7000 feet), apply:Environment, Operating:Temperature 10° to 35°C (50°F to 95°F)Relative Humidity 20% - 80%Maximum Dew Point 21°C (70°F)Environment, Nonoperating:Temperature 10°C to 52°C (50°F to 125°F)Rel Humidity 8% - 80%Maximum Wet Bulb 27°C (80°F)Maximum Dew Point 21°C (70°F)Environment, Shipping:Temperature -40°C to 60°C (-40°F to 140°F)Relative Humidity 5% - 100% (no condensation)Maximum Wet Bulb 29°C (84°F)Environment, Storage: All ModelsTemperature 1°C to 60°C (34°F to 140°F)Relative Humidity 5% -80%Maximum Wet Bulb 29°C (84°F)Note:Prior to the installation of an IBM system, careful consideration should begiven to the computer room environment. If there is any question aboutpotential corrosive gases or level of particulates, contact your IBMrepresentative for assistance in monitoring the environment.Figure B-1. Table - Environmental SpecificationsLevel 04a, June 21, 2004© Copyright IBM Corp. 2002, 2004 B-1