W415-1935 / A / 05.07.19EN22venting installationFor optimum performance, it is recommended that all horizontal runs have a minimum of 1/4" (6mm) rise per footusing flexible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.! WARNING• Ensure to unpack all loose materials from inside the firebox prior to connecting the gas and electrical supply• If your appliance is supplied with a remote, ensure the remote receiver is in the “OFF” position priorto connecting the gas and electrical supply to the appliance.• For safe and proper operation of the appliance, follow the venting instructions exactly.• The appliance exhaust flue collar must be sealed using Mill Pac. All exhaust and intake vent pipe jointsmust be sealed using red RTV high temp silicone sealant (W573-0002) (not supplied) or black high temp MillPac (W573-0007) (not supplied).• If using pipe clamps to connect rigid vent components, a minimum of 3 screws must also be used to ensurethe connection cannot slip off.• Do not clamp the flexible vent pipe.• Risk of fire, explosion, or asphyxiation. Improper support of the entire venting system may allow vent to sagand separate. Use vent run supports and connect vent sections per installation instructions.• Risk of fire, do not allow loose materials or insulation to touch the vent pipe. Remove insulation to allow for theinstallation of the attic shield and to maintain clearances to combustibles.• Do not fill the space between the vent pipe and enclosure with any type of material. Do not pack insulationor combustibles between ceiling firestops. Always maintain specifi ed clearances around venting and fi restopsystems. Install wall shields and firestops as specifi ed. Failure to keep insulation or other materials away fromvent pipe may cause fire.4.0 venting installation