14-11FP0Item Add-ress Name Defaultvalue Descriptions402 Pulse catch inputfunction settingsNot set(H0)The checked contacts are set aspulse catch input.In FP Programmer II, enter the abovesettings in hexadecimal.Example:When X3 and X4 are set as pulsecatch inputWith the FP0, settings X6 and X7 areinvalid.Using FPWIN GRThe checked contacts are set asinterrupt input.Inputsetting403 Interrupt input settings Not set(H0)Specify the effective interrupt edge.(When set: ON→OFF is valid)Using FP Programmer IIExample:When setting inputs X0, X1, X2 andX3 as interrupts, and X0 and X1 areset as interrupt inputs when goingfrom on to off.Note1) With the TOOL software, “0” or “1” is set for each bit on the screen in the setting for systemregister 403.Note2) If system register 400 to 403 are set simultaneously for the same inptu relay, the followingprecedence order is effective:[High-speed counter] ‘[Pulse catch]’ [Interrupt input].When the high-speed counter is being used in the incremental input mode, even if input X0 isspecified as an interrupt input and as pulse catch input, those settings are invalid, and input X0functions as counter input for the high-speed counter.No. 400: H1 a This setting will be valid. No. 402: H1 No. 403: H1