S−LINK Control UnitFP04 − 74.3 Wiring the Power Supply4.3 Wiring the Power SupplyWith the FP0 S−LINK control unit, power must be supplied at two locations (powersupply connector and S−LINK terminal block).4.3.1 Wiring to Power Supply ConnectorThis is the power supply for the programmable controller section and the S−LINKcontroller in the S−LINK control unit (24V DC, 150mA).Powersupplycable4.3.2 Wiring to S−LINK Terminal BlockThis is the power supply for the S−LINK controller in the S−LINK control unit and otherS−LINK input/output devices to which power is supplied through the 24V − 0V line ofthe S−LINK main cable.The current consumption for the overall S−LINK system is calculated by referring to thesection entitled “Determining the Power Supply” in the “S−LINK Design Manual.” (Forstandard purposes, a power supply exceeding 24V DC, 1.6 A should be selected.)0V+24VFrom externalpower supplySupplied to S−LINKinput/output devicesBrownBlueWhiteBlackSupply of power to S−LINK terminal blocknext page