B-6 Sequencing LogicAC30 series Variable Speed InverterExample Comms Control Words (hexadecimal):CC77 STOP (Normal) or go to SWITCHED ON stateCC7F RUNCC7B QUICKSTOPCC7D COAST STOPCCF0 FAULT RESETStatus WordThe Status Word provides the detailed status of the sequencer. Regardless of the source of the Control Word, this is always available as 0661Status Word.Bit Name Description0 Ready To Switch On Drive initialised and not in Configuration mode1 Switched On Drive in SWITCHED ON or OPERATION ENABLED state2 Operation Enabled Running (or stopping)3 Faulted Unacknowledged fault present4 Voltage Enabled Line supply present5 Quickstop Inactive = 0 when reacting to a Quickstop request6 Switch On Disabled Drive in SWITCH ON DISABLED state7 unused8 unused9 Control From Comms Using 0627 Comms Control Word as the Control Word source10 unused11 unused12 Jog Operation Using Jog Reference or will use Jog Reference when Operation Enabled13 Reverse Operation Running backwards or will run backward when Operation Enabled14 Reference From Comms Using 0681 Comms Reference as the Reference source15 Stopping Operation Enable command removed or Quickstop active