C-94 Parameter ReferenceAC30 series Variable Speed DriveIO ConfigureSetup::Inputs and OutputsParameters::Inputs And Outputs::IO ConfigureThese parameters are used to configure the input signal processing.Parameter Name No. Path Default Range Units WritableAnin 01 Type 0001 Setup::Inputs and Outputs::Base IOParameters::Inputs And Outputs::IOConfigure0 0:-10..10 V1:0..10 V2:0..20 mA3:4..20 mAALWAYSAnalog input 1 is associated with terminal X11.1The signal processing electronics for analog input 1 supports four input ranges.Anin 01 Offset 0957 Setup::Inputs and Outputs::Base IOParameters::Inputs And Outputs::IOConfigure0.00 Min to Max % ALWAYSThe offset is expressed as a percentage of the hardware range selected by 0001 Anin 01 Type. For example, with the 4..20mA rangean offset of 10% is equivalent to 1.6mA on the input.The offset is added to the measured value.Anin 01 Scale 0958 Same as PNO 957 1.0000 Min to Max ALWAYSThe scale is a simple multiplication factor. The input voltage or current is converted to a percentage value. 0957 Anin 01 Offset isadded and the result is multiplied by 0958 Anin 01 Scale. The result is presented in parameter 0039 Anin 01 Value.Anin 02 Type 0002 Same as PNO 1 0 0:-10..10 V1:0..10 VALWAYSAnalog input 2 is associated with terminal X11.2The signal processing electronics for analog input 2 supports two input ranges.