C-158 Parameter ReferenceAC30 series Variable Speed DriveRaise LowerSetup::Application::Raise LowerMonitor::Application::Raise Lower*Appears when the Raise/Lower macro is selected.The Raise/Lower function acts as an internal motorised potentiometer (MOP) used as a reference source.Parameter Name No. Path Default Range Units WritableRL Ramp Time 1901 Setup::Application::Raise Lower 10.0 0.0 to 600.0 s ALWAYSRate of change of the Output. Defined as the time to change from 0.00% to 100.00% . Note that the raise and lower rates are alwaysthe same.L Reset Value 1902 Setup::Application::Raise Lower 0.0 -500.0 to 500.0 % ALWAYSThe value Output is set to when the Reset Input is TRUE.RL Maximum Value 1903 Setup::Application::Raise Lower 100.0 -500.0 to 500.0 % ALWAYSThe maximum value to which Output will ramp up to.RL Minimum Value 1904 Setup::Application::Raise Lower -100.0 -500.0 to 500.0 % ALWAYSThe minimum value to which Output will ramp down to.Reset InputThis is connected to a Digital Input as part of the selected Macro. When TRUE forces Output to track Reset Value.Raise InputThis is connected to a Digital Input as part of the selected Macro. When TRUE causes Output to ramp up.