wc_tx003618gb_FM10.fm59Mobile Generator Operation (Basler Controller)7.7 Using the Lugs and the Convenience ReceptaclesOverview Loads can be connected to the genset in two different ways:1. At the connection lugs (r).Located as shown, behind the lug door, the connection lugs serve as connectionpoints for cables.2. At the convenience receptacles:■ 120V/240V twist-lock receptacles (l)■ 120V GFCI duplex receptacles (m)Note: The convenience receptacles are not protected by the main circuit breaker.They are protected by their own circuit breakers (j, k). Power to the conveniencereceptacle circuit breakers is available any time the engine is running, even withthe main circuit breaker OFF (open).Note: Graphic is representative only. Your machine may vary.Lug doorinterlockswitchThe lug door interlock switch (p) is located behind the lug door. The lug doorinterlock switch is a safety device. When the lug door is opened, the lug doorinterlock switch trips the main circuit breaker.Note: The lug door interlock switch does NOT interrupt power to the conveniencereceptacles. However, the switch does stop excitation at the generator. The resultis significantly reduced voltage at the convenience receptacles.wc_gr011537ljprj km