wc_tx003618gb_FM10.fm66Mobile GeneratorOperation (Basler Controller)7.11 Stopping the MachineCheck with other personnel on the jobsite and let them know that power is beingturned off. Make sure that the power shutdown will not create any hazards byturning off devices such as pumps, heaters, or lights that may need to be kept on.1. Turn off all loads connected to the generator.2. Set the main circuit breaker to OFF.3. Set the convenience receptacle circuit breakers to OFF.4. Let the engine run for approximately ten minutes to cool it down.5. Move the engine start switch to the OFF position.7.12 Emergency Stop SwitchLocation The emergency stop switch (a) is the red button located as shown, and can beaccessed with the panel doors closed.Function Activate the emergency stop switch by pushing the red button. Pushing theemergency stop switch:■ turns off (opens) the main circuit breaker■ cuts power to the fuel solenoid■ stops the engine■ causes “Alarm Active: Emergency Stop” to appear on the LCD displayThe emergency stop switch will remain activated until the button is pulled out.NOTICE: Do not use the emergency stop switch to shut down the generator duringnormal operation. The emergency stop switch is intended for use only in an actualemergency situation where the generator must be stopped immediately.To shut down the generator during normal operation, turn off (open) the main circuitbreaker and then move the engine start switch to the OFF position.ALARM ACTIVEALARM ACTIVETO VIEWTO VIEWEMERGENCY STOPEMERGENCY STOPaEMERGENCYwc_gr010365