4 Option ComponentsYASKAWA SIEP YEACOM 06 V1000 Option PROFINET SI-EP3/V Technical Manual 12Table 3 Option LED States Power-Up DiagnosticsAn LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. Afterthe LEDs have completed the diagnostic LED sequence, the option is successfully initialized. The LEDs then assumeoperational conditions as shown in Table 3.Table 4 Power-Up Diagnostic LED SequenceName Indication Operating Status RemarksColor StatusMS(visible throughdrive cover)– OFF Power supply OFF Power is not being supplied to the drive.Green ON Option operating The option is operating normally andinitialization is complete.Green Flashing (1) Diagnostics Diagnostic data available.Green Flashing (2) Configuration tool Identified by a configuration tool.Red ON Default MAC or fatal error occurred. Default MAC address has been programmed orthe option has detected an unrecoverable error.Red Flashing (1) Configuration error (non-fatal) Configuration error.Red Flashing (2) No IP (non-fatal) No IP address assigned.Red Flashing (3) No station name (non-fatal) No station name assigned.Red Flashing (4) Init failure (non-fatal) Failed to initialize module.Green/Red Flashing Option self-test The option is in self-test mode.NS(visible throughdrive cover)– OFF Offline or Power supply OFF –Green ON Connected Connection established with I/O controller andin RUN mode.Green Flashing Connected and stopped Connection established with I/O controller andin STOP mode.Red ON BUS fault Unrecoverable BUS fault.Red Flashing (1) Lost communication Host communication is temporarily lost.Red Flashing (2) Lost link No link detected to network.10/100(visible atRJ45 jack)Yellow OFF 10 Mbps is established –Yellow ON 100 Mbps is established –LINK/ACT(visible atRJ45 jack)Green OFF Link is not established –Green ON Link is established –Green Flashing Link is established and there is networkactivity –Sequence Module Status (MS) Network Status (NS) Time (ms)1 Green OFF 2502 Red OFF 2503 Green OFF -4 Green Green 2505 Green Red 2506 Green OFF -