8 Communication39 YASKAWA SIEP YEACOM 06 V1000 Option PROFINET SI-EP3/V Technical Manual Option Low Priority Alarm CodesThese codes are transmitted as Manufacturer Specific Diagnostic low priority alarms that can be seen in the PLCconfiguration software. These low priority codes are the same codes that appear in the drive manual, except with an offsetof 0x1000.Table 25 PROFINET Option Low Priority Alarm CodesDrive AlarmCode(hex) <1><1> Drive error code is stored in MEMOBUS/Modbus address 0080 hex.<2> Not available in V1000-series drives.Description Drive AlarmCode(hex) <1>Description0401 Undervoltage (Uv) 0420 MEMOBUS/Modbus Test Mode Fault (SE)0402 Overvoltage (ov) 0422 Motor Overheat (oH3)0403 Heatsink Overheat (oH) 0427 PID Feedback Loss (FbL)0404 Drive Overheat (oH2) 0428 PID Feedback Loss (FbH)0405 Overtorque 1 (oL3) 042A Drive Disabled (dnE)0406 Overtorque 2 (oL4) 042B PG Disconnected (PGo) <2>0407 Rum Command Input Error (EF) 0431 Option Watchdog Error (E5)0408 Drive Baseblock (bb) 0432 Option Station Address Setting Error (AEr)0409 External Fault 3, input terminal S3 (EF3) 0433 Option Comm. Cycle Setting Error (CyC)040A External Fault 3, input terminal S4 (EF4) 0434 High Current Alarm (HCA)040B External Fault 3, input terminal S5 (EF5) 0435 Cooling Fan Maintenance Time (LT-1)040C External Fault 3, input terminal S6 (EF6) 0436 Capacitor Maintenance Time (LT-2)040D External Fault 3, input terminal S7 (EF7) 0438 Option EEPROM Error (EEP)040E External Fault 3, input terminal S8 (EF8) <2> 0439 External Fault (input terminal S1) (EF1)040F Cooling Fan Error (FAn) 043A External Fault (input terminal S2) (EF2)0410 Overspeed (oS) 043B Safe Disable Input (HbbF)0411 Excessive Speed Deviation (dEv) 043C Safe Disable Input (Hbb)0412 PG Disconnected (PGo) <2> 043D Mechanical Weakening Detection 1 (oL5)0414 MEMOBUS/Modbus Comm. Error (CE) 043E Mechanical Weakening Detection 2 (UL5)0415 Option Communication Error (bUS) 043F PLC Alarm (PA1)0416 Serial Comm. Transmission Error (CALL) 0440 PLC Alarm (PA2)0417 Motor Overload (oL1) 0441 Output Voltage Detection Fault (voF)0418 Drive Overload (oL2) 0442 IGBT Maintenance Time (90%) (TrPC)041A Option Card External Fault (EF0) 0443 Soft Charge Bypass Relay Maintenance Time (LT-3)041B Motor Switch Command Input during Run (rUn) 0444 IGBT Maintenance Time (50%) (LT-4)041D Serial Comm. Transmission Error (CALL) 0445 Braking Transistor Overload (boL)041E Undertorque Detection 1 (UL3) 0448 Motor Overheat (NTC Input) (oH5)041F Undertorque Detection 2 (UL4) 0449 DriveWorksEZ Alarm (dWAL)