9 Web InterfaceYASKAWA SIEP YEACOM 06 V1000 Option PROFINET SI-EP3/V Technical Manual 44 Email AlertsTabThe Email Alerts tab allows the user to configure four Email Fault/Alarm conditions. When the condition is true, oneemail will be sent to the provided email address. Another email will not be sent until the condition becomes false and thentrue again. A 30-second timer prevents emails from being sent when conditions reoccur immediately after being removed.The timer helps limit the amount of emails sent regarding the same intermittent condition and helps to reduce networktraffic by reducing emails about reoccurring errors.Figure 28Figure 28 Email Alerts Tab View Procedure: Conditional Email Set-up1. Define the condition that will trigger the email by selecting a monitor parameter, a comparator, and a value. Setup comparator values for the range of values to check in the chosen condition. If choosing only one condition andno OR or AND are needed, set the “OR/AND” drop-down selection to “NotUsed”.2. Enter the email address where the alert will be sent.3. Enter the message that will appear in the email contents.4. Enter the email subject.5. Click the “Email Active” checkbox to enable the alert.Clicking “Save to device” will save the entered information into the option memory.Clicking “Cancel and reload” will cancel any pending edits and display the most recently saved settings from the optionboard.