6 Option Drive Parameters23 YASKAWA SIEP YEACOM 06 V1000 Option PROFINET SI-EP3/V Technical ManualTable 7 Option MonitorsF7-23 to F7-27 <5>Dynamic Output AssemblyParameters Configurable outputs 1 to 5. 0F7-33 to F7-37 <5>Dynamic Input AssemblyParameters Configurable inputs 1 to 5. 0H5-11 Communications ENTERFunction SelectionSelect the function for the ENTER command that saves parameter data tothe drive.0: Parameter changes are activated when ENTER command is written1: Parameter changes are activated immediately without use of ENTERcommand1<1> To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control the drive frequency referencevia the master device, set b1-01 to 3.<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error or an EF0 fault is detected. Take proper safety measures, such asinstalling an emergency stop switch.<3> Software versions 1012 and later have F6-07 and F6-08 both set to 1.<4> Software versions 1014 and earlier have F7-14 default of 0.<5> If a value other than 0 is assigned to parameters F7-23 to F7-27 and F7-33 to F7-37 by the drive, that value will take precedent over a value setby the configuration software. If the value in the drive is 0 (default), the value from the configuration software is used.No. Name Description Value RangeU6-80 to U6-83 Online IP Address SI-EP3/V IP Address, U6-80 is the most significant octet. 0 to 255U6-84 to U6-87 Online Subnet Subnet, U6-94 is the most significant octet. 0 to 255U6-88 to U6-91 Online Gateway Gateway, U6-88 is the most significant octet. 0 to 255U6-92 Online Speed Port 1 Link Speed 10, 100U6-93 Online Duplex Port 1 Duplex Setting 0: Half, 1: FullU6-94 Online Duplex Port 2 Link Speed 0: Half, 1: FullU6-95 Online Duplex Port 2 Duplex Setting 0: Half, 1: FullU6-98 First Fault First Option Board Fault -U6-99 Current Fault Current Option Board Fault -No. Name Description Default