5 Installation Procedure15 YASKAWA SIEP YEACOM 06 V1000 Option PROFINET SI-EP3/V Technical ManualTable 5 Installation Steps Based on Drive Model3. For IP20/Open-Chassis models CIMR-V
A
B, Remove the bottom cover of the drive by applyingpressure to the tabs on each side of the bottom cover. Pull the bottom cover away from the drive while pushing inon the tabs to release the cover from the drive. Refer to Figure 5 for details.Refer to Figure 6 for drive models CIMR-V
BA0006B to BA0018B, 2A0010B to 2A0069B, and 4A0001B to4A0038B, which require removing the terminal cover prior to removing the bottom cover.Figure 5Figure 5 Remove the Bottom Cover on an IP20/Open-Chassis Drive(Models CIMR-V
BA0001B to BA0003B and 2A0001B to 2A0006B)Figure 6Figure 6 Remove the Terminal Cover and Bottom Cover on an IP20/Open-Chassis Drive(Models CIMR-V
BA0006B to BA0018B; 2A0010B to 2A0069B; 4A0001B to 4A0038B)4. On IP20/Open-Chassis models, connect the drive side of the ground wire to the drive ground terminal.Note: The four different ground wires packaged with the option connect the option to different drive models. Select the proper groundwire depending on drive size.Figure 7Figure 7 Connect the Ground Wire on an IP20/Open-Chassis Drive5. For IP20/Open-Chassis models, go to Step 9. on page 17.Enclosure Type Drive Model Proceed to Step PageIP20/Open-Chassis CIMR-V
A
B 3. 15IP20/NEMA Type 1 <1><1> Installing the option on an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while maintaining IP20 conformity.CIMR-V
A
F 4. 15Ground terminalGround wireGround wireDrive-sideconnectorScrew size:M3.5 to M6Option unitconnectorScrew size: M3