Detailed Description• To display the frequency reference as a percent rather than hertz, set o1-03 to 1.• To display the reference in r/min, set o1-03 to 2. The drive will calculate the revolutions per minute from the maximum output frequency and the numberof motor poles. Motor pole data should be set to parameters E2-04, E4-04, and E5-04.• To display the revolutions of the machine (r/min) or the line speed (m/min), set o1-03 to 3, and then set parameters o1-10 and o1-11.n o1-10: Frequency Reference Setting and User-Set DisplayDetermines how values are set and displayed when operating at the max output frequency.No. Parameter Name Setting Range Defaulto1-10 Frequency Reference Setting and User-Set Display1 to 60000: User-set display□□□□□o1-10: The decimal pointwas removed.5 figure digits are setDetermined by o1-03n o1-11: Frequency Reference Setting / Decimal DisplaySets the number of digits for setting and displaying the frequency reference.No. Parameter Name Setting Range Defaulto1-11 Frequency Reference Setting / Decimal Display0: No decimal point.1: Set to one decimal point.2: Set to the second decimal point.3: Set to the third decimal point.Determined by o1-03u o2: Operator Key SelectionsThese parameters determine the functions assigned to the operator keys.n o2-01: LOCAL/REMOTE Key Function SelectionParameter o2-01 determines whether the LOCAL/REMOTE switch on the digital operator will be enabled and will switch between keypad operation andthe sources specified by the b1-01 and b1-02 parameters when the drive is stopped.No. Parameter Name Setting Range Defaulto2-01 LOCAL/REMOTE Key Function Selection 0: Disabled1: Enabled 1Note: When LOCAL has been selected, the LO/RE indicator light is on. The user cannot switch between LOCAL/REMOTE while the drive is running the motor.Detailed DescriptionThere are three different ways to switch between LOCAL and REMOTE.• Switching between LOCAL and REMOTE using the LO/RE key:Step Display/Result1. Power up the drive. should be lit. ⇒2. If is not lit, press the key. Press again to put the drive back into REMOTE mode. ⇒ STOP • Switching between LOCAL and REMOTE with an input terminal (S1 through S7):Note: For more details on multi-function input settings, Refer to H1: Multi-Function Contact Inputs on page 160. Taking the steps described here will disable the LO/RE key onthe operator keypad.Step Display/Result1. Power up the drive. ⇒2. Press the key until the parameter settings screen appears. ⇒3. Press to enter the parameter settings menu. ⇒4. Scroll to H1-05 (or any parameter between H1-05 and H1-07) by pressing and . ⇒5. Press to display the value set to H1-05 ⇒6. Press to select the flashing digit. ⇒7. Press to set “01” (LOCAL/REMOTE). ⇒5.10 o: Digital Operator Related Settings206 YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)