B.2 Parameter Tableu A: Initialization ParametersThe A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor Control Method, Password,User Parameters and more.No. Name Description Range Def.ControlMode Addr.Hex Pg.V/f OLV PMA1: Initialization ParametersUse A1 parameters to configure the basic environment for drive operation.A1-01 <22><16> Access Level SelectionSelects which parameters are accessible via the digital operator.0: Operation only1: User Parameters (access to a set of parameters selected by the user)2: Advanced Access Level0 to 2 2 A A A 101H —A1-02 Control Method SelectionSelects the Control Method of the drive.0: V/f Control without PG2: Open Loop Vector (OLV)5: PM Open Loop Vector (PM)Note: Does not return to the default setting when the drive is initialized.0, 2, 5 0 S S S 102 75A1-03 Initialize ParametersResets all parameters to factory default settings. (Initializes the drive then returnsA1-03 to 0)0: No Initialize1110: User Initialize(First set user parameter values must be stored using parameter o2-03)2220: 2-Wire Initialization3330: 3-Wire Initialization5550: OPE04 Error Reset0 to 3330 0 A A A 103 —The following parameters are not reset when the performinginitialization:A1-00, A1-02, A1-07, and all U2 and U3 monitors.A1-04 Password 1When the value set into A1-04 does not match the value set into A1-05,parameters A1-01 thru A1-03, A1-06, and A2-01 thru A2-32 cannot be changed.0 to 9999 0 A A A 104 —A1-05 Password 20 to 9999 0 A A A 105 —This parameter is hidden from view. To access A1-05,first display A1-04. Then press the STOP key whileholding down the up arrow key. Parameter A1-05 willappear.—A1-06 Application PresetSets parameters that are commonly used in certain applications to A2-01 throughA2-16 for easier access.0: General-purpose (A2 parameters are not affected)1: Water supply pump2: Conveyor3: Exhaust fan4: HVAC fan5: Air compressor6: Crane (Hoist)7: Crane (Travelling)0 to 7 0 A A A 127 —A1-07 DriveWorksEZ Function Selection0: Disabled1: Enabled2: Multi-function input (enabled when H1-oo = 9F)0 to 2 0 A A A —A2: User ParametersUse A2 parameters to program the drive.A2-01 toA2-32 User Parameters, 1 to 32 Parameters that were recently edited are listed here. The user can also selectparameters to appear here for quick access.Parameters will be stored here for quick access when A1-01 = 1. b1-01 to o2-08 -- <16> A A A 106 to 125 —A2-33 User Parameter Automatic Selection0: Parameters A2-01 through A2-32 are reserved for the user to create a list ofUser Parameters.1: Save history of recently viewed parameters. Recently edited parameters willbe saved to A2-17 through A2-32 for quick access.0, 1 1 <4> A A A 126 —<4> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not = 0.<16> Default setting value is dependent on parameter A1-06, Application Selection.<22> Parameter can be changed during run.u b: ApplicationApplication parameters configure the Run Command Source, DC Injection Braking, Speed Search, Timer functions, PID control, the Dwell function,Energy Savings and a variety of other application-related settings.No. Name Description Range Def.ControlMode Addr.Hex Pg.V/f OLV PMb1: Operation Mode SelectionUse b1 parameters to configure the operation mode.b1-01 Frequency Reference Selection 1Selects the frequency reference input source.0: Operator - Digital preset speed d1-01 to d1-17.1: Terminals - Analog input terminal A1 or A2.2: MEMOBUS/Modbus communications3: Option PCB4: Pulse Input (Terminal RP)0 to 4 1 S S S 180 76b1-02 Run Command Selection 1Selects the run command input source.0: Operator - RUN and STOP keys on the digital operator.1: Digital input terminals S1 to S72: MEMOBUS/Modbus communications3: Option PCB.0 to 3 1 S S S 181 77B.2 Parameter TableYASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary) 295B Parameter List