n Jog Operation ProceduresSet H1-07 (Multi-Function Contact Input Terminal S7 Function Selection) to “12” (FJOG command).Step Display/Result1. Turn the power on to the drive. The initial display appears.2. Press the key until the Parameter Setting menu appears.3. Press to enter the Parameter Setting menu.4. Press and until H1-07 appears. Note: Select a parameter between H1-01 and H1-07.5. Press and set the value for H1-07.6. Press and until “12” appears on the screen.Note: At jog operation in reverse run, set multi-function contact input to 13.7. Press to save the setting.To begin rotating the motor:Step Display/Result1. Turn the power on to the drive. The initial display appears.Note: Set the drive to REMOTE.2. With multi-function contact input terminal S7 closed, the motor rotates forwards at 6 Hz.Note: No run command is necessary when using the Jog frequency.Motor3. The drive will stop with terminal S7 open.u Multi-Step Speed Operation (4-Step Speed)Select up to 17 preset references (including Jog reference) using five multi-function inputs S3 through S7. Four multi-step references can be selected usingtwo multi-function inputs as illustrated in Figure 4.32 .n Multi-Step Speed Operation ParametersNo. Name Descriptiond1-01 Frequency Reference 1 Frequency reference. o1-03 determines the units, with Hz as the default.d1-02 Frequency Reference 2 Frequency reference when multi-function input “Multi-Step Speed Reference 1" (H1-oo = 3) is on. Setting unit: set by o1-03.d1-03 Frequency Reference 3 Frequency reference when multi-function input “Multi-Step Speed Reference 2” (H1-oo = 4) is on. Setting unit: set by o1-03.d1-04 Frequency Reference 4 Frequency reference when multi-function input “Multi-Step Speed Reference 1, 2" (H1-oo = 3 and 4) are both on. Setting unit: setby o1-03.n Digital InputTerminal Parameter Setting ContentsS5 H1-05 3 Multi-Step Speed Reference 1S6 H1-06 4 Multi-Step Speed Reference 2n Wiring ExampleSet up external switches SW1 and SW2.R/L1S/L2T/L3U/T1V/T2W/T3MThree-Phase, 200 Vac(AC400 V)S5S6SW1SW2SCDriveFigure 4.32 Control Terminals for 4 Multi-Step Speeds4.7 Test Run98 YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)