No. Name Description Range Def.ControlMode Addr.Hex Pg.V/f OLV PMC6-03 Carrier Frequency Upper Limit Open Loop Vector: C6-03 defines the fixed carrier frequency if C6-02 = F.V/f control: C6-03 and C6-04 set upper and lower limits for the carrierfrequency.carrier frequencyE1-04max outputfrequencyoutput frequency× (C6-05) × K outputfrequencyC6-03C6-04The coefficient K depends on C6-03:C6-03 ≥ 10.0 kHz: K = 310.0 kHz > C6-03 ≥ 5.0 kHz: K = 25.0 kHz > C6-03: K = 1When C6-05 ≤ 6, C6-04 is disabled (makes the carrier frequency C6-03 value).1.0 to 15.0 <8> A A A 225 —C6-04 Carrier Frequency Lower Limit 0.4 to 15.0 <8> A - - 226 —C6-05 Carrier Frequency Proportional Gain Sets the relationship of output frequency to carrier frequency when C6-02 =F. 00 to 99 <8> A - - 227 —<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control.<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control.<3> Default setting value is dependent on parameters o2-04, Drive/kVA Selection, A1-02, Control Method Selection and C6-01, Normal/Heavy Duty selection. 351.<6> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range becomes 0.00 to 600.00 seconds.<8> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.<22> Parameter can be changed during run.<23> Parameter cannot be changed during run when parameter A1-02 = 5-PM OLV Control.u d: ReferencesReference parameters are used to set the various frequency reference values during operation.No. Name Description Range Def.ControlMode Addr.Hex Pg.V/f OLV PMd1: Frequency ReferenceUse d1 parameters to configure the drive frequency reference.d1-01 <22> Frequency Reference 1 Frequency reference 0.00 to 400.00Hz <11><19>0.00 Hz S S S 280 76d1-02 <22> Frequency Reference 2 Frequency reference when digital input "Multi-Step Speed Reference 1" (H1-oo= 3) is on. 0.00 Hz S S S 281 76d1-03 <22> Frequency Reference 3 Frequency reference when digital input "Multi-Step Speed Reference 2” (H1-oo= 4) is on. 0.00 Hz S S S 282 76d1-04 <22> Frequency Reference 4 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2" (H1-oo = 3 and 4) are on. 0.00 Hz S S S 283 76d1-05 <22> Frequency Reference 5 Frequency reference when digital input "Multi-Step Speed Reference 3" (H1-oo= 5) is on. 0.00 Hz A A A 284 —d1-06 <22> Frequency Reference 6 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 3 " (H1-oo = 3 and 5) are on. 0.00 Hz A A A 285 —d1-07 <22> Frequency Reference 7 Frequency reference when digital inputs "Multi-Step Speed Reference 2, 3" (H1-oo = 4 and 5) are on. 0.00 Hz A A A 286 —d1-08 <22> Frequency Reference 8 Frequency reference when multi-function input "Multi-Step speed reference 1, 2,3" (H1-oo = 3, 4, 5) are on. 0.00 Hz A A A 287 —d1-09 <22> Frequency Reference 9 Frequency reference when multi-function input "Multi-Step Speed Reference4" (H1-oo = 32) is on. 0.00 Hz A A A 288 —d1-10 <22> Frequency Reference 10 Frequency reference when digital input "Multi-Step Speed Reference 1, 4" (H1-oo = 3 and 32) are on. 0.00 Hz A A A 28B —d1-11 <22> Frequency Reference 11 Frequency reference when digital inputs "Multi-Step Speed Reference 2, 4" (H1-oo = 4 and 32) are on. 0.00 Hz A A A 28C —d1-13 <22> Frequency Reference 13 Frequency reference when digital inputs "Multi-Step Speed Reference 3, 4" (H1-oo = 5 and 32) are on. 0.00 Hz A A A 28E —d1-14 <22> Frequency Reference 14 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 3, 4" (H1-oo = 3, 5, 32) are on. 0.00 Hz A A A 28F —d1-15 <22> Frequency Reference 15 Frequency reference when digital inputs "Multi-Step Speed Reference 2, 3, 4" (H1-oo = 4, 5, 32) are on. 0.00 Hz A A A 290 —d1-16 <22> Frequency Reference 16 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2, 3,4" (H1-oo = 3, 4, 5, 32) are on. 0.00 Hz A A A 291 —d1-17 <22> Jog Frequency ReferenceFrequency reference when digital inputs "Jog Frequency Reference", "Forward Jog"or "Reverse Jog." are on. "Jog Frequency Reference" has priority over "Multi-StepSpeed Reference 1 to 16”. 6.00 Hz S S S 292 76d2: Frequency Upper and Lower LimitsUse d2 parameters to configure the frequency reference limits.d2-01 Frequency Reference Upper Limit Sets the frequency reference upper limit as a percentage of maximum outputfrequency (E1-04). Output speed is limited to this value even if the frequencyreference is higher. This limit applies to all frequency reference sources. 0.0 to 110.0 100.0% A A A 289 —d2-02 Frequency Reference Lower Limit Sets the frequency reference lower limit as a percentage of maximum outputfrequency (E1-04). Output speed is limited to this value even if the frequencyreference is lower. This limit applies to all frequency reference sources. 0.0 to 110.0 0.0% A A A 28A —B.2 Parameter Table300 YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)