Setting Specification Characteristic ApplicationC 90 Hz (with 60 Hz base)Constant output When operating at speeds greater than 60 Hz motor requires constant voltage.Above 60 Hz, motor operates in constant power range.D 120 Hz (with 60 Hz base)E 180 Hz (with 60 Hz base)n V/f Pattern CharacteristicsThese graphs apply to 200 V class drives; double the values for 400 V class drives.• Constant Torque Characteristics, Settings 0 through 3Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 HzVoltage (V)Frequency (Hz)0122001.3 2.5 5016Voltage (V)Frequency (Hz)012162001.5 3 60Voltage (V)Frequency (Hz)012162001.5 3 6050Voltage (V)Frequency (Hz)012162001.5 3 7260• Reduced Torque Characteristics, Settings 4 through 7Setting = 4 50 Hz Setting = 5 50 Hz Setting = 6 60 Hz Setting = 7 60 HzVoltage (V)Frequency (Hz)082001.3 25 5035Voltage (V)Frequency (Hz)092001.3 25 5050Voltage (V)Frequency (Hz)082001.5 30 6035Voltage (V)Frequency (Hz)092001.5 30 6050• High Starting Torque Characteristics, Settings 8 through BSetting = 8 50 Hz Setting = 9 50 Hz Setting = A 60 Hz Setting = B 60 Hz0122001.3 2.5 5019Voltage (V)Frequency (Hz)Voltage (V)Frequency (Hz)0132001.3 2.5 5024Voltage (V)Frequency (Hz)0122001.5 3 6019Voltage (V)Frequency (Hz)0152001.5 3 6024• Constant Output Characteristics, Settings C through FSetting = C 90 Hz Setting = D 120 Hz Setting = E 180 HzVoltage (V)Frequency (Hz)012162001.5 3 9060Voltage (V)Frequency (Hz)012162001.5 3 12060Voltage (V)Frequency (Hz)012162001.5 3 18060Note: Setting an improper V/f pattern may result in reduced motor torque or increased current (due to over excitation).u Motor Parameters: E2-01 through E2-12 (Manually Entering Parameter Settings)In Open Loop Vector Control, motor parameters are set automatically during the Auto-Tuning process. Manually set motor parameters if Auto-Tuningcannot be performed. Refer to Auto-Tuning on page 91 for more information. Refer to E: Motor Parameters for a list of motor parameters E2-01 toE2-12.n Setting Motor Parameters ManuallyThe following table provides instructions on how to set motor parameters. Refer to the motor data sheet for the correct motor data.No. Parameter Name Setting MethodE2-01 Motor Rated Current Sets the motor nameplate full load current in amperes (A).E2-02 Motor Rated Slip Calculate and set the motor rated slip based on the rated speed described on the motor nameplate.Motor rated slip = Motor rated frequency [Hz] - Rated speed [r/min] x No. of motor poles / 120.E2-03 Motor No-Load Current Set motor no-load current at rated voltage and rated frequency.Contact the motor manufacturer to get the no-load current. This information is not usually written on the motor nameplate.The default no-load current is for a Yaskawa 4-pole motor.E2-04 Number of Motor Poles Displayed only when OLV control mode is selected. Set the number of motor poles described on the motor nameplate.4.6 Basic Drive Setup AdjustmentsYASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary) 854 Start-Up Programming& Operation