Setting Function Page4E <1> Braking Transistor Fault (rr) 1944F <1> Braking Resistor Overheat (rH) 19490 DriveWorksEZ Digital Output 119491 DriveWorksEZ Digital Output 292 DriveWorksEZ Digital Output 3Setting Function Page100 to 192 H2 Parameter Functions Reversed OutputSwitching of 0 to 92 195<1> Available in drive software versions PRG: 1016 and later.Setting 0: During RunOutput closes when the drive is outputting a voltage.Status DescriptionOpen Drive is stopped.Closed A Run command is input or the drive is during deceleration or during DC injection.ONONOFFOFFONOFFRun commandBaseblockcommandOutputfrequencyDuring RunFigure 5.55 During Run Time ChartSetting 1: Zero SpeedTerminal closes whenever the output frequency falls below the minimum output frequency set to E1-09.Status DescriptionOpen Output frequency is above the minimum output frequency set to E1-09Closed Output frequency is less than or equal to the minimum output frequency set to E1-09OFFOutput frequencyormotor speedZero Speed ONE1-09 (Max. Output Frequency)Figure 5.56 Zero-Speed Time ChartSetting 2: Speed Agree 1 (fref/fout Agree 1)Closes whenever the actual output frequency is within the Speed Agree Width (L4-02) of the current frequency referenceregardless of the direction.Status DescriptionOpen Output frequency does not match the frequency reference while the drive is running.Closed Output frequency is within the range of frequency reference ± L4-02.Note: Detection works in both directions, forward and reverse.5.7 H: Terminal FunctionsYASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual 1875 Parameter Details