6.6 Operator Programming ErrorsAn Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an individual parameter settingis inappropriate.The drive will not operate until the parameter is set correctly; however, no alarm or fault outputs will occur. If an oPEoccurs, investigate the cause and Refer to oPE Codes, Causes, and Possible Solutions on page 274 for the appropriateaction. When an oPE error is displayed, press the ENTER button to display U1-18 (oPE fault constant). This monitordisplays the parameter causing the oPE error.u oPE Codes, Causes, and Possible SolutionsTable 6.11 oPE Codes, Causes, and Possible SolutionsLED Operator Display Error NameoPE01 Drive Capacity Setting FaultDrive capacity and the value set to o2-04 do not match.Cause Possible SolutionsThe drive capacity setting (o2-04) and the actual capacity of the drive arenot the same. Correct the value set to o2-04.LED Operator Display Error NameoPE02 Parameter Range Setting ErrorUse U1-18 to find parameters set outside the range.Cause Possible SolutionsParameters were set outside the possible setting range. Set parameters to the proper values.Note: Other errors are given precedence over oPE02 when multiple errors occur at the same time.LED Operator Display Error NameoPE03Multi-Function Input Selection ErrorA contradictory setting is assigned to multi-function contact inputs H1-01to H1-07.Cause Possible Solutions• The same function is assigned to two multi-function inputs.• Excludes “Not used” and “External Fault.”• Ensure all multi-function inputs are assigned to different functions.• Re-enter the multi-function settings to ensure this does not occur.The Up command was set but the Down command was not, or vice versa(settings 10 vs. 11). Correctly set functions that need to be enabled in combination with otherfunctions.The Up 2 command was set but the Down 2 command was not, or viceversa (settings 75 vs. 76).• Run/Stop command for a 2-Wire sequence 2 was set (H1-oo = 42),but forward/reverse command (H1-oo = 43) was not.• “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A orH1-02 = 6A).Correctly set functions that need to be enabled in combination with otherfunctions.Two of the following functions are set at the same time:• Up/Down Command (10 vs. 11)• Up 2/Down 2 Command (75 vs. 76)• Hold Accel/Decel Stop (A)• Analog Frequency Reference Sample/Hold (1E)• Offset Frequency 1, 2, 3 Calculations (44, 45, 46)• Check if contradictory settings have been assigned to the multi-function input terminals at the same time.• Correct setting errors.The Up/Down command (10, 11) is enabled at the same time as PID control(b5-01). Disable control PID (b5-01 = “0”) or disable the Up/Down command.6.6 Operator Programming Errors274 YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual