Table B.7 Three-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD settingsNo. Description Unit Default Settings− Model − 2A0001 2A0002 2A0004 2A0006 2A0008o2-04 Drive Model Selection − 96 (60H) 97 (61H) 98 (62H) 99 (63H) 100 (64H)C6-01 Normal/Heavy Duty − HD ND HD ND HD ND HD ND HD ND0 1 0 1 0 1 0 1 0 1E2-11(E4-11,T1-02) Motor rated power kW 0.1 0.2 0.2 0.4 0.4 0.75 0.75 1.1 1.1 1.5b3-06 Speed Search current 1 − 1.0 1.0 1.0 1.0 1.0 1.0 0.5 0.5 0.5 0.5b3-08 Current Control Gain during SpeedSearch (Speed Estimation Type) – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5b8-04 Energy saving coefficient − 481.7 356.9 356.9 288.2 288.2 223.7 223.7 196.6 196.6 169.4C6-02 Carrier frequency − 4 7 4 7 4 7 4 7 3 7E2-01(E4-01,T1-04) Motor rated current A 0.6 1.1 1.1 1.9 1.9 3.3 3.3 4.9 4.9 6.2E2-02(E4-02) Motor rated slip Hz 2.5 2.6 2.6 2.9 2.9 2.5 2.5 2.6 2.6 2.6E2-03(E4-03) Motor no-load current A 0.4 0.8 0.8 1.2 1.2 1.8 1.8 2.3 2.3 2.8E2-05(E4-05) Motor line-to-line resistance Ω 35.98 20.56 20.56 9.84 9.842 5.156 5.156 3.577 3.577 1.997E2-06(E4-06) Motor leakage inductance % 21.6 20.1 20.1 18.2 18.2 13.8 13.8 18.5 18.5 18.5E2-10(E4-10) Motor Iron Loss W 6 11 11 14 14 26 26 38 38 53E5-01 Motor Code hex FFFF FFFF FFFF FFFF 0002 0002 0003 0003 FFFF FFFFL2-02 Momentary power loss ride-through time s 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3L2-03 Momentary power loss Baseblocktime s 0.2 0.2 0.2 0.2 0.2 0.3 0.3 0.4 0.4 0.4L2-04 Momentary power loss voltagerecovery time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3L2-05 Uv detection voltage V dc 190 190 190 190 190 190 190 190 190 190L3-24 Motor acceleration time s 0.178 0.178 0.178 0.178 0.178 0.142 0.142 0.142 0.142 0.166L8-02 Overheat alarm level °C 110 110 110 110 115 115 100 100 100 100L8-09 Ground fault selection − 0 0 0 0 0 0 0 0 0 0L8-35 Installation method selection − 0 0 0 0 0 0 0 0 0 0L8-38 Carrier frequency reductionselection − 1 1 1 1 1 1 1 1 1 1n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10 10 10n2-01 Speed Feedback Detection Control(AFR) Gain – 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00B.6 Defaults by Drive Model and Duty Rating (ND/HD)384 YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual