No. Name Description Range Def.ControlMode Addr.Hex Pg.V/fOLVPMb1-08 Run Command Selectionwhile in Programming Mode0: Run command accepted only in the operation menu.1: Run command accepted in all menus.2: Prohibit entering Programming Mode during Run 0 to 2 0 A A A 187 122b1-14 Phase Order SelectionSets the phase order for drive output terminals U/T1, V/T2and W/T3.0 : Standard1 : Switch phase order0, 1 0 A A A 1C3 123b1-15 Frequency ReferenceSelection 2Selects the frequency reference input source 2.0: Operator - Digital preset speed d1-01 to d1-17.1: Terminals - Analog input terminal A1 or A22: MEMOBUS communications3: Option PCB4: Pulse Input (Terminal RP)0 to 4 0 A A A 1C4 123b1-16 Run Command Selection 2Selects the run command input source 2.0: Operator - RUN and STOP keys on the digital operator.1: Digital input terminals2: MEMOBUS communications3: Option PCB0 to 3 0 A A A 1C5 123b1-17 Run Command at PowerUpDetermines the operation when a Run command is active atpower up of the drive.0: Run command not issued, needs to be cycled1: Run command issued, motor operation start0, 1 0 A A A 1C6 123b2: DC Injection BrakingUse b2 parameters to configure DC Injection Braking operationb2-01 DC Injection Braking StartFrequencySets the frequency at which DC Injection Braking startswhen Ramp to Stop (b1-03 = 0) is selected. If b2-01< E1-09,DC Injection Braking starts at E1-09.0.0 to10.0 0.5Hz A A A 189 123b2-02 DC Injection BrakingCurrent Sets the DC Injection Braking current as a percentage of thedrive rated current. 0 to 75 50% A A A 18A 124b2-03 DC Injection Braking Time/DC Excitation Time atStartSets DC Injection Braking time at start. Disabled when setto 0.00 seconds. 0.00 to10.000.00 s<1> A A A 18B 124b2-04 DC Injection Braking Timeat StopSets DC Injection Braking time at stop.When b1-03 = 2, actual DC Injection time is calculated asfollows:(b2-04) x 10 x (Output Freq)/(E1-04). When b1-03 = 0, thisparameter sets the amount of DC Injection time applied tothe motor at the end of the decel ramp or High Slip Braking.Disabled when set to 0.00.0.00 to10.00 0.50 s A A − 18C 124b2-08 Magnetic FluxCompensation Value Sets the magnetic flux compensation as a percentage of theno-load current value (E2-03). 0 to 1000 0% − A − 190 124b2-12 Short Circuit Brake Time atStartSets the time for Short-Circuit brake operation at start.Disabled when set to 0.00.<2>0.00 to25.50 0.00 s − − A 1BA 124b2-13 Short Circuit Brake Time atStopSets the Short-Circuit brake operation time at stop. Used tostop a motor rotating due to inertia. Disabled when set to 0.00seconds.<2>0.00 to25.50 0.50 s − − A 1BB 125b3: Speed SearchUse b3 parameters to configure Speed Search function operation.b3-01 Speed Search Selection atStartEnables/disables the Speed Search function at start.0: Disabled - Speed Search is not automatically performedat start.1: Enabled - Speed Search is automatically performed atstart.0, 1 0 A A A 191 128b3-02 Speed Search DeactivationCurrentSets the current level at which the speed is assumed to bedetected and Speed Search is ended. Set as a percentage ofthe drive rated current. 0 to 200 120<3> A A − 192 128b3-03 Speed Search DecelerationTimeSets the time constant used to reduce the output frequencyduring Speed Search. Related to a change from max. outputfrequency to 0.0.1 to10.0 2.0 s A A − 193 128b3-05 Speed Search Delay Time Delays the Speed Search operation after a momentary powerloss to allow time for an external output contactor to close. 0.0 to 100 0.2 s A A A 195 128b3-06 Output Current 1 duringSpeed SearchSets the current injected to the motor at the beginning ofEstimation type Speed Search. Set as a factor of the motorrated current. 0.0 to 2.0 <4> A A − 196 128B.2 Parameter TableYASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual 333B Parameter List