148 Actual signals and parametersParameter listingParameter data is specific to ACS320 firmware version 4.01C. Group 99: Start-up dataThis group defines special Start-up data required to:• set up the drive• enter motor information.Note: Parameters checked under the heading “S” can be modified only when thedrive is stopped.Group 99: Start-up dataCode Description Range Resolution Default S9901 LANGUAGE 0...25 1 0Selects the display language.9902 APPLIC MACRO -3...21 1 1 Selects an application macro. Application macros automatically edit parameters toconfigure the ACS320 for a particular application. See Application macros forapplication macro descriptions.9905 MOTOR NOM VOLT 115 … 345 V (200 V, US)230 … 690 V (400 V, US)288 … 862 V (600 V, US)1 V1 V1 V230 V460 V575 VDefines the nominal motor voltage.• Must equal the value on the motor ratingplate.• Sets the maximum drive output voltagesupplied to the motor.• Drive cannot supply the motor with avoltage greater than the mains voltage.9906 MOTOR NOM CURR 0.15*I2N … 1.5*I2N 0.1 A 1.5*I2N Defines the nominal motor current.• Must equal the value on the motor rating plate.0= ENGLISH 1= ENGLISH (AM) 2= DEUTSCH 3= ITALIANO4= ESPAÑOL 5= PORTUGUES 6= NEDERLANDS 7= FRANCAIS8= DANSK 9= SUOMI 10= SVENSKA 11= RUSSKI12= POLSKI 13= TÜRKCE 14= CZECH 15= MAGYAR16= ELLINIKA 17= CHINESE 18= KOREAN 19= JAPANESE1= HVAC DEFAULT 2= SUPPLY FAN 3= RETURN FAN 4= CLNG TWR FAN5= CONDENSER 6= BOOSTER PUMP 7= PUMP ALTERNA 8= INT TIMER9= INT TIMER CS 10= FLOATING PNT 11= DUAL SETPPID 12= DL SP PID CS13= E -BYPASS 14= HAND CONTROL 15= E-CLIPSE 21= AC500 MODBUSOutput voltageOutput9907frequency9905