Start-up 754. Highlight the desired value for the target drive.5. Press SAVE to save setting.6. Press EXIT to step back to the differences view and continue for each remainingexception.7. When your editing is complete, press READY in the Differences List and thenselect “Yes, save parameters.”Download failuresIn some situations, the drive may be unable to accept a download. In those cases,the control panel display is: “Parameter download failed” plus one of the followingcauses:• Set not found – You are attempting to download a data set that was not defined inthe backup. The remedy is to manually define the set, or upload the set from adrive that has the desired set definitions.• Par lock – The remedy is to unlock the parameter set (parameter 1602PARAMETER LOCK).• Incompatible drive/model – The remedy is to perform backups only betweendrives of the same type and the same model.• Too many differences – The remedy is to manually define a new set, or upload theset from a drive that more closely resembles the target drive.Note: If upload or download of parameters is aborted, the partial parameter set is notimplemented. Clock set modeThe clock set mode is used for setting the time and date for the internal clock of thedrive. To use the timer functions of the drive, the internal clock has to be set first. Dateis used to determine weekdays and is visible in Fault logs.To set the clock, follow these steps:1Select MENU to enter the mainmenu.2Scroll to CLOCK SET with theUP/DOWN buttons and selectENTER to enter the Time & datemode.0 A0 %0 mA0.0.0. 0.0HzOFFMENUSPASSISTANTSCHANGED PARCLOCK SETEXIT ENTEROFF MAIN MENU 5