384 Technical dataRatingsNote: When choke is not used, input current is effected by supply network andimpedance.Use the table in Fuses and alternate short-circuit protection (page 388) to correctlysize the input cabling as well as input fuses or MMP for branch circuit protection.Sizing will be determined by the actual input current which is dependent on the inputline voltage and the input choke selection and rated motor current. If motor ratedcurrent is below I 2N , I1N is reduced relatively.Type code Input Output Framesizewithout chokeor reactorwith choke or5% reactorACS320- I1N I1N(480 V) I1N I1N(480 V) I LD2) I2N I2max3) PNx = E/U 1) A A A A A A A kW hp1-phase supply voltage 200…240 V units (Confirm output ratings meet motor requirements)01x-02A4-2 6.1 - 4.5 - 2.3 2.4 4.0 0.37 0.5 R001x-04A7-2 11.4 - 8.1 - 4.5 4.7 7.9 0.75 1 R101x-06A7-2 16.1 - 11.0 - 6.5 6.7 11.4 1.1 1.5 R101x-07A5-2 16.8 - 12.0 - 7.2 7.5 12.6 1.5 2 R201x-09A8-2 21.0 - 15.0 - 9.4 9.8 16.5 2.2 3 R23-phase supply voltage 200…240 V units03x-02A6-2 4.7 - 2.6 - 2.4 2.6 4.2 0.37 0.5 R003x-03A9-2 6.7 - 3.9 - 3.5 3.9 6.1 0.55 0.75 R003x-05A2-2 8.4 - 5.2 - 4.7 5.2 8.2 0.75 1 R103x-07A4-2 13.0 - 7.4 - 6.7 7.4 11.7 1.1 1.5 R103x-08A3-2 13.2 - 8.3 - 7.5 8.3 13.1 1.5 2 R103x-10A8-2 15.7 - 10.8 - 9.8 10.8 17.2 2.2 3 R203x-14A6-2 23.9 - 14.6 - 13.3 14.6 23.3 3 3 R203x-19A4-2 27.3 - 19.4 - 17.6 19.4 30.8 4 5 R203x-26A8-2 45.0 - 26.8 - 24.4 26.8 42.7 5.5 7.5 R303x-34A1-2 55.0 - 34.1 - 31.0 34.1 54.3 7.5 10 R403x-50A8-2 76.0 - 50.8 - 46.2 50.8 80.9 11.0 15 R43-phase supply voltage 380…480 V units03x-01A2-4 2.4 2.0 1.3 1.1 1.1 1.2 2.1 0.37 0.5 R003x-01A9-4 4.0 3.3 2.0 1.7 1.7 1.9 3.3 0.55 0.75 R003x-02A4-4 4.5 3.8 2.5 2.1 2.2 2.4 4.2 0.75 1.0 R103x-03A3-4 6.6 5.5 3.5 2.9 3.0 3.3 5.8 1.1 1.5 R103x-04A1-4 7.6 6.3 3.8 3.2 3.7 4.1 7.2 1.5 2.0 R103x-05A6-4 10.6 8.8 5.3 4.4 5.1 5.6 9.8 2.2 3.0 R103x-07A3-4 12.8 10.7 6.8 5.7 6.6 7.3 12.8 3.0 3.0 R103x-08A8-4 15.0 12.5 8.6 7.2 8.0 8.8 15.4 4.0 5.0 R103x-12A5-4 20.7 17.2 12.3 10.3 11.4 12.5 21.9 5.5 7.5 R3