Actual signals and parameters 279Default values with different macrosWhen application macro is changed (9902 APPLIC MACRO), the software updatesthe parameter values to their default values. The table below shows the parameterdefault values for different macros. For other parameters, the default values are thesame for all macros. See the parameter list starting on page 148.Index Name/Selection HVACDEFAULT SUPPLY FAN RETURN FAN CLNG TWRFAN CONDENSER BOOSTERPUMP PUMPALTERNA9902 APPLICMACRO 1 = HVACDEFAULT 2 = SUPPLYFAN 3 = RETURNFAN 4 = CLNGTWR FAN 5 =CONDENSER 6 =BOOSTERPUMP7 = PUMPALTERNA1001 EXT1COMMANDS 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI11002 EXT2COMMANDS 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI11003 DIRECTION 1 =FORWARD 1 =FORWARD 1 = FORWARD 1 =FORWARD 1 = FORWARD 1 = FORWARD 1 = FORWARD1102 EXT1/EXT2SEL 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT11103 REF1 SELECT 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI11106 REF2 SELECT 19 =PID1OUT 19 =PID1OUT 19 = PID1OUT 19 =PID1OUT 19 = PID1OUT 19 =PID1OUT 19 =PID1OUT1201 CONSTSPEED SEL 3 = DI3 3 = DI3 3 = DI3 3 = DI3 3 = DI3 3 = DI3 0 = NOT SEL1304 MINIMUM AI2 20.0% 20.0% 20.0% 20.0% 20.0% 20.0% 20.0%1401 RELAYOUTPUT 1 1 = READY 7 =STARTED 7 = STARTED 1 = READY 1 = READY 1 = READY 31 = PFA1601 RUN ENABLE 0 = NOT SEL 2 = DI2 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL1805 DO SIGNAL 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN2008 MAXIMUMFREQ 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz2201 ACC/DEC 1/2SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL2202 ACCELERTIME 1 30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 10.0 s 10.0 s2203 DECELERTIME 1 30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 10.0 s 10.0 s3019 COMM FAULTTIME 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s4001 GAIN 2.5 2.5 2.5 2.5 2.5 2.5 2.54002 INTEGRATIONTIME 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s4101 GAIN 2.5 2.5 2.5 2.5 2.5 2.5 2.54102 INTEGRATIONTIME 3.0 s 3.0 s 3.0 s 3.0 s 60.0 s 3.0 s 3.0 s8116 AUX MOTSTOP D 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s 3.0 s8118 AUTOCHNGINTERV 0.0 =NOT SEL0.0 =NOT SEL 0.0 =NOT SEL 0.0 =NOT SEL 0.0 =NOT SEL 0.0 =NOT SEL 0.0 =NOT SEL8123 PFA ENABLE 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 1 = ACTIVE