37User Manual MN04200002EEffective January 2016C441 Ethernet module user manual(C441R, C441T, C441U, C441V)EATON www.eaton.comTable 68. Assembly Instance 60 (0x3C): Basic Softstarter InputByte OffsetWordOffsetSize(bytes) Name Description0 0 1 BasicSoftstarterInputBasic softstart Input.Bit = Description0 = Faulted2 = Running17 = Bypass (at reference)Total Assembly Size (bytes): 1Table 69. Assembly Instance 61 (0x3D): Extended SoftstarterInputByteOffset WordOffset Size(bytes) Name Description0 0 1 ExtendedSoftstarterInputExtended Softstart InputBit = Description0 = Faulted1 = Warning2 = Running13 = Running2 (Ramp2)4 = Ready5 = CtrlFromNet7 = Bypass (at reference).Total Assembly Size (bytes): 1Table 70. Assembly Instance 101 (0x65): Extended SoftstarterOutput with Relay OutsByte OffsetWordOffsetSize(bytes) Name Description0 0 1 ExtendedSoftstarter Extended softstart assembly wrelay outputs.Bit = Description0 = Run 11 = Run 2 (Ramp2)2 = Fault Reset4 = C441 Q1 relay out5 = C441 Q2 relay outTotal Assembly Size (bytes): 1Table 71. Assembly Instance 102 (0x66): Device StatusByteOffsetWordOffsetSize(bytes) Name Description0 0 2 DeviceStatus Device Status Bit Array0 Running - RUN command active1 Jogging - Jog command active2 Permissive - Start allowed (must be1 to start)3 Ramp2 - Ramp2 settings active4 Local Control (0 - network; 1 - local)5 Faulted - S811+ fault present6 Warning - S811+ warning present(self clearing)7 In bypass - S811+ Bypass closed8 = Output 19 = Output 210 = Input 111 = Input 212 = Input 313 = Input 414 = Alarm No Trip Enabled15 = S811+ Internal Comm LossTotal Assembly Size (bytes): 2Table 72. Assembly Instance 110 (0x6E): Status and Current (A)Assembly includes the status overview and motor current levels scaled in Amps.Word Size (bytes): 2ByteOffsetWordOffsetSize(bytes) Name Description0 0 2 DeviceStatus Device Status Bit Array0 Running - RUN command active1 Jogging - Jog command active2 Permissive - Start allowed (must be1 to start)3 Ramp2 - Ramp2 settings active4 Local Control (0 - network; 1 - local)5 Faulted - S811+ fault present6 Warning - S811+ warning present(self clearing)7 In bypass - S811+ Bypass closed8 = Output 19 = Output 210 = Input 111 = Input 212 = Input 313 = Input 414 = Alarm No Trip Enabled15 = S811+ Internal Comm Loss2 1 6 3Ph RMSLineCurrent(amps)Scaled RMS 3phase line current - This isthe actual current flowing to the motorin 1.0A.Total Assembly Size (bytes): 8Table 73. Assembly Instance 111 (0x6F): Status andCurrent (0.1A)Assembly includes the status overview and motor current levels scaled in 0.1As.Word Size (bytes): 2ByteOffset WordOffset Size(bytes) Name Description0 0 2 Device Status Device Status Bit Array0 Running - RUN command active1 Jogging - Jog command active2 Permissive - Start allowed (must be1 to start)3 Ramp2 - Ramp2 settings active4 Local Control (0 - network; 1 - local)5 Faulted - S811+ fault present6 Warning - S811+ warning present(self clearing)7 In bypass - S811+ Bypass closed8 = Output 19 = Output 210 = Input 111 = Input 212 = Input 313 = Input 414 = Alarm No Trip Enabled15 = S811+ Internal Comm Loss2 1 6 3Ph RMSLine Current(deciamps)Scaled RMS 3phase line current - This isthe actual current flowing to the motorin 0.1A.Total Assembly Size (bytes): 8