38User Manual MN04200002EEffective January 2016C441 Ethernet module user manual(C441R, C441T, C441U, C441V)EATON www.eaton.comTable 74. Assembly Instance 120 (0x78): Status measurementand Thermal (A)Includes the Motor status, motor Ave Current scaled in Amps and Thermal valueWord Size (bytes): 2ByteOffset WordOffset Size(bytes) Name Description0 0 2 Device Status Device Status Bit Array0 Running - RUN command active1 Jogging - Jog command active2 Permissive - Start allowed (must be1 to start)3 Ramp2 - Ramp2 settings active4 Local Control (0 - network; 1 - local)5 Faulted - S811+ fault present6 Warning - S811+ warning present(self clearing)7 In bypass - S811+ Bypass closed8 = Output 19 = Output 210 = Input 111 = Input 212 = Input 313 = Input 414 = Alarm No Trip Enabled15 = S811+ Internal Comm Loss2 1 2 3Ph AveLine Current(amps)Scaled RMS average of the 3 phaseline current - This is the actual currentflowing to the motor in 1.0A.4 2 1 % ThermalPile used Thermal Pile Used Percentage - Trip at100%6 3 2 Motor ControlFaults S811+ Motor Control Fault Bit FieldBit Fault0 Phaseloss1 Phase Imbalance2 Thermal Pile3 Overcurrent4 Breaker Fault5 GND Fault6 Motor Stall7 Motor Jam8 OverTemp9 UnderLoad10 Reserved11 Estop12 Reserved13 Reserved14 Reserved15 OtherTotal Assembly Size (bytes): 8Table 75. Assembly Instance 121 (0x79): Status measurementand Thermal (0.1A)Includes the Motor status, motor Ave Current scaled in 0.1A and Thermal valueWord Size (bytes): 2ByteOffset WordOffset Size(bytes) Name Description0 0 2 DeviceStatus Device Status Bit Array0 Running - RUN command active1 Jogging - Jog command active2 Permissive - Start allowed (must be 1to start)3 Ramp2 - Ramp2 settings active4 Local Control (0 - network; 1 - local)5 Faulted - S811+ fault present6 Warning - S811+ warning present (selfclearing)7 In bypass - S811+ Bypass closed8 = Output 19 = Output 210 = Input 111 = Input 212 = Input 313 = Input 414 = Alarm No Trip Enabled15 = S811+ Internal Comm Loss2 1 2 3Ph AveLineCurrent(deciamps)Scaled RMS average of the 3 phase linecurrent - This is the actual current flowingto the motor in 0.1A.4 2 1 % ThermalPile used Thermal Pile Used Percentage - Trip at100%6 3 2 MotorControlFaultsS811+ Motor Control Fault Bit FieldBit Fault0 Phaseloss1 Phase Imbalance2 Thermal Pile3 Overcurrent4 Breaker Fault5 GND Fault6 Motor Stall7 Motor Jam8 OverTemp9 UnderLoad10 Reserved11 Estop12 Reserved13 Reserved14 Reserved15 OtherTotal Assembly Size (bytes