39User Manual MN04200002EEffective January 2016C441 Ethernet module user manual(C441R, C441T, C441U, C441V)EATON www.eaton.comTable 77. Assembly Instance 131 (0x83):Status,Current,Voltage,Thermal (0.1A)Assembly includes the status overview, motor current levels scaled in 0.1A, Pole Voltages& Thermal.Word Size (bytes): 2ByteOffset WordOffset Size(bytes) Name Description0 0 2 DeviceStatus Device Status Bit Array0 Running - RUN command active1 Jogging - Jog command active2 Permissive - Start allowed (must be 1to start)3 Ramp2 - Ramp2 settings active4 Local Control (0 - network; 1 - local)5 Faulted - S811+ fault present6 Warning - S811+ warning present (selfclearing)7 In bypass - S811+ Bypass closed8 = Output 19 = Output 210 = Input 111 = Input 212 = Input 313 = Input 414 = Alarm No Trip Enabled15 = S811+ Internal Comm Loss2 1 6 3Ph RMSLine Current(deciamps)Scaled RMS 3phase line current - This is theactual current flowing to the motor in 0.1A.8 4 1 % ThermalPile used Thermal Pile Used Percentage - Trip at100%10 5 2 Averagecurrent as% FLAAverage of the 3 phase current as apercentage of the Motor Nameplatefla setting12 6 6 3Ph RMSMainsVoltage3 Phase RMS Mains voltage reading (involts)Total Assembly Size (bytes): 18Table 76. Assembly Instance 130 (0x82):Status,Current,Voltage,Thermal (A)Assembly includes the status overview, motor current levels scaled in Amps, PoleVoltages & Thermal.Word Size (bytes): 2ByteOffset WordOffset Size(bytes) Name Description0 0 2 DeviceStatus Device Status Bit Array0 Running - RUN command active1 Jogging - Jog command active2 Permissive - Start allowed (must be 1to start)3 Ramp2 - Ramp2 settings active4 Local Control (0 - network; 1 - local)5 Faulted - S811+ fault present6 Warning - S811+ warning present (selfclearing)7 In bypass - S811+ Bypass closed8 = Output 19 = Output 210 = Input 111 = Input 212 = Input 313 = Input 414 = Alarm No Trip Enabled15 = S811+ Internal Comm Loss2 1 6 3Ph RMSLine Current(amps)Scaled RMS 3phase line current - This isthe actual current flowing to the motor in1.0A.8 4 1 % ThermalPile used Thermal Pile Used Percentage - Trip at100%10 5 2 Averagecurrent as% FLAAverage of the 3 phase current as a per-centage of the Motor Nameplate fla setting12 6 6 3Ph RMSMainsVoltage3 Phase RMS Mains voltage reading (involts)Total Assembly Size (bytes): 18