52User Manual MN04200002EEffective January 2016C441 Ethernet module user manual(C441R, C441T, C441U, C441V)EATON www.eaton.comTable 99. Registers Available with C441 Motor Insight (Cont.)StartCoil RegisterRead/Write Name Description (Units)- 327 R RemainingUnderloadTrip RestartDelayLoad Fault - Time to Restart ( sec )- 328 R/W Run TimeHours Motor Run Time in hours (resettable) ( hr )- 329 R Start Count Start Count (Resettable)- 330 R Trip Reason 0x0001 - Restart Attempts Exceeded0x0002 - Relay Turned Off (Network/UI)0x0004 - Contactor Failure0x0008 - Under Current Trip0x0010 - Overload Trip0x0020 - GND Fault Trip0x0040 - Current Unbalance Trip0x0080 - Current Single Phase0x0100 - Reserved (0)0x0200 - High Power Trip0x0400 - Over Voltage Trip0x0800 - Under Voltage Trip0x1000 - Voltage Unbalance Trip0x2000 - Over Current Trip0x4000 - Low Power Trip0x8000 - Phase Reversal Trip- 331 R OverloadStatus Overload Status- 0x0001: Overload Trip- 0x0002: Ground Fault Trip- 0x0004: High Power Trip- 0x0080: Relay Closed- 332 R Error Code Warning/Alarm Indications0x0001 (1) - Low Voltage Warning0x0002 (2) - High Voltage Warning0x0004 (4) - Voltage Unbalance Warning0x0008 (8) - Low Power Warning0x0010 (16) - Reverse Phase Warning0x0020 (32) - Current Unbalance Warning0x0040 (64) - Voltage Single PhaseWarning0x0080 (128) - Current Single PhaseWarning0x0100 (256) - GND Fault Warning- 333 R C441 DSPFW Version C441 DSP Firmware Version- 334 R UI FirmwareVersion User Interface Firmware Version- 335 R/W C441 Unit ID Unit ID0x00BA (186) - C441BA0x00BB (187) - C441BB0x00CA (202) - C441CA0x00CB (203) - C441CB0x00DA (218) - C441DA0x00DB (219) - C441DB0x00EA (234) - C4410109(x)0x00EB (235) - C4410590(x)5361 336 R Aux RelayTrip Reason 0x0002 - Relay Turned Off (Network/UI)0x0004 - Contactor Failure0x0008 - Under Current Trip0x0010 - Overload Trip0x0020 - GND Fault Trip0x0040 - Current Unbalance Trip0x0080 - Current Single Phase0x0100 - Mains Freq Fault0x0200 - High Power Trip0x0400 - Over Voltage Trip0x0800 - Under Voltage Trip0x1000 - Voltage Unbalance Trip0x2000 - Over Current Trip0x4000 - Low Power Trip0x8000 - Phase Reversal TripTable 99. Registers Available with C441 Motor Insight (Cont.)StartCoil RegisterRead/Write Name Description (Units)- 400 R/W Commandregister 0x0066 - Clear Motor Run Hours0x0077 - Clear Fault Queue 10x0078 - Clear Fault Queue0x0088 - Network watchdog enable0x0099 - Network watchdog disable0x00AA - Reset Relay0x00BB - Clear Motor Start Count0x00CC - Force Ground Fault0x00DD - Fault Relay OFF0x00EE - Reset Auxiliary Relay (120 VacControl Power models only)- 401 R/W MotorControl -- 402 R/W ConfigurationReset 1 = Soft Reset (equivalent to a powercycle)2 = Factory Reset- 403 R/W CT Multiplier For 90 Amp Units: 1-4, number of conduc-tors through CT.For 9 Amp Units: 1-2, number of conduc-tors through CT;For 9 Amp Units, CT multipliers: 3 (150:5),4 (300:5), 5 (600:5)- 404 R/W Ground FaultPick-up Level Ground Fault Pick-up Level ( x0.01A )- 405 R/W UnderCurrent Pick-up LevelUnder Current Pick-up Level ( % )- 406 R/W Low PowerPick-up Level Low Power Pick-up Level ( x0.01kW )- 407 R/W Overload FLA Motor Full Load Current ( x0.01A )- 408 R/W CurrentUnbalancePick-up LevelCurrent Unbalance Pick-up Level ( % )- 409 R/W Overload TripClass Overload Trip Class- 410 R/W UnderVoltage Pick-up LevelUnder Voltage Pick-up Level ( V )- 411 R/W Over VoltagePick-up Level Over Voltage Pick-up Level ( V )- 412 R/W VoltageUnbalancePick-up LevelVoltage Unbalance Pick-up Level ( % )- 413 R/W Jam Pick-upLevel Jam Pick-up Level ( % )- 414 R/W High KW Triplimit High Power Pick-up Level ( x0.01kW )- 415 R/W Phase Order Phase Order- 0 (Trip Disabled)- 1 ACB- 2 ABC- 416 R/W Supply FaultHold-off Time Restart Delay ( sec )- 417 R/W Motor FaultHold-off Time Motor Fault Reset Delay ( min )- 418 R/W Load FaultHold-off Time Load Fault Reset Delay ( min )- 419 R/W Load FaultNumber ofRestartsLoad Fault Number of Reset Attempts0: Manual1-45: Automatic- 420 R/W Motor FaultNumber ofRestartsMotor Fault Number of Attempts:0: Manual1-45: Automatic- 421 R/W Ground FaultTrip Delay Ground Fault Pickup Delay ( sec )- 422 R/W UnderCurrent TripDelayUnder Current Trip Delay ( sec )- 423 R/W Low PowerTrip Delay Low Power Trip Delay ( sec )- 424 R/W Jam TripDelay Jam Trip Delay ( sec )