41User Manual MN04200002EEffective January 2016C441 Ethernet module user manual(C441R, C441T, C441U, C441V)EATON www.eaton.comTable 79. Assembly Instance 141 (0x8D): Full S811 Monitoring,Current in 0.1A (Cont.)ByteOffset WordOffset Size(bytes) Name Description36 18 2 MotorControlWarningsS811+ Motor Control Warning Bit FieldBit Warning0 Phaseloss1 Phase Imbalance2 Thermal Pile3 Overcurrent4 Breaker Fault5 GND Fault6 Motor Stall7 Motor Jam8 OverTemp9 UnderLoad10 Reserved11 Reserved12 Reserved13 Reserved14 Reserved15 Other38 19 6 Active FaultList Will display up to 3 faults/warnings thatare actively present44 22 4 Total MotorStarts Number of motor startsTotal Assembly Size (bytes): 48Table 79. Assembly Instance 141 (0x8D): Full S811 Monitoring,Current in 0.1AIncludes the most common measurement values. Current values scaled in 0.1AWord Size (bytes): 2ByteOffset WordOffset Size(bytes) Name Description0 0 2 DeviceStatus Device Status Bit Array0 Running - RUN command active1 Jogging - Jog command active2 Permissive - Start allowed (must be 1to start)3 Ramp2 - Ramp2 settings active4 Local Control (0 - network; 1 - local)5 Faulted - S811+ fault present6 Warning - S811+ warning present (selfclearing)7 In bypass - S811+ Bypass closed8 = Output 19 = Output 210 = Input 111 = Input 212 = Input 313 = Input 414 = Alarm No Trip Enabled15 = S811+ Internal Comm Loss2 1 6 3Ph RMSLine Current(deciamps)Scaled RMS 3phase line current - This isthe actual current flowing to the motor in0.1A.8 4 2 3Ph AveLine Current(deciamps)Scaled RMS average of the 3phase linecurrent - This is the actual current flowingto the motor in 0.1A.10 5 2 Averagecurrent as %FLAAverage of the 3 phase current as a per-centage of the Motor Nameplate fla setting12 6 1 % ThermalPile used Thermal Pile Used Percentage - Trip at100%14 7 6 3Ph RMSMainsVoltage3 Phase RMS Mains voltage reading (involts)20 10 2 Ave 3PhReal Power(kW)Average 3 phase real power (in kW)22 11 2 Power Factor Power factor reading 0 - 1.0000 (in 0.0001)24 12 1 Field Inputs A bitfield representing the input points.Bit = Description0 = Input 11 = Input 22 = Input 33 = Input 426 13 6 Power PoleTemperature S811+ power pole temperature in 0.1degrees C32 16 2 LineFrequency Frequency reading of incoming mains volt-age (in 0.01Hz)34 17 2 MotorControlFaultsS811+ Motor Control Fault Bit FieldBit Fault0 Phaseloss1 Phase Imbalance2 Thermal Pile3 Overcurrent4 Breaker Fault5 GND Fault6 Motor Stall7 Motor Jam8 OverTemp9 UnderLoad10 Reserved11 Estop12 Reserved13 Reserved14 Reserved15 Other