47User Manual MN04200002EEffective January 2016C441 Ethernet module user manual(C441R, C441T, C441U, C441V)EATON www.eaton.comTable 87. Class 140 (0x8C): Device Status Object (Cont.)Attrib NV Access DataType Name Description8(0x08) V Get UINT Bit field(warn-ings)S811+ Motor Control Warning Bit FieldBit Warning0 Phaseloss1 Phase Imbalance2 Thermal Pile3 Overcurrent4 Breaker Fault5 GND Fault6 Motor Stall7 Motor Jam8 OverTemp9 UnderLoad10 Reserved11 Reserved12 Reserved13 Reserved14 Reserved15 Other9(0x09) V Get UINT MostrecentfaultS811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue10(0x0A) V Get UINT nextmostrecentfaultS811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue11(0x0B) V Get UINT nextmostrecentfaultS811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue12(0x0C) V Get UINT nextmostrecentfaultS811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue13(0x0D) V Get UINT nextmostrecentfaultS811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue14(0x0E) V Get UINT nextmostrecentfaultS811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue15(0x0F) V Get UINT nextmostrecentfaultS811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue16(0x10) V Get UINT nextmostrecentfaultS811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue17(0x11) V Get UINT nextmostrecentfaultS811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue18(0x12) V Get UINT Oldestfault S811+ fault QueueQueue will hold up to the last 10 faults -Fault codes are not repeated in queue19(0x13) V Set/Get BOOL ClearFaultQueueSet this parameter to TRUE to clear thefault queue.Table 88. Class 147 (0x93): Voltage Monitor ObjectInstance Count: 1Instance List: 1Attrib NV Access DataType Name Description1(0x01) V Get UINT 3Ph RMSMainsVoltage3 Phase RMS Mains voltage reading(in volts)(L1-L2)2(0x02) V Get UINT 3Ph RMSMainsVoltage3 Phase RMS Mains voltage reading(in volts)(L2-L3)3(0x03) V Get UINT 3Ph RMSMainsVoltage3 Phase RMS Mains voltage reading(in volts)(L3-L1)4(0x04) V Get UINT LineFrequency Frequency reading of incoming mainsvoltage (in 0.01Hz)5(0x05) V Get USINT IncomingPhaseSequencePhase sequence of incoming mainsvoltage0 - ABC1 - ACB6(0x06) V Get UINT DC ControlVoltage DC Control Voltage reading in 0.001V7(0x07) NV Set/Get UINT Motor RatedVolts Rated voltage of the motor8(0x08) NV Set/Get USINT UnderVoltage TripEnableUnder voltage trip enable0x00 - disable0x01 - fault enable0x02 - warning enable9(0x09) NV Set/Get USINT UnderVoltage TripThresholdUnder voltage trip threshold (in per-cent of rated motor voltage)10(0x0A) NV Set/Get UINT UnderVoltage TripDurationAmount of time an under voltagecondition must exist before a trip; 0.0 -60.0 (in 0.1secs)11(0x0B) NV Set/Get USINT Over VoltageTrip Enable Over voltage trip enable0x00 - disable0x01 - fault enable0x02 - warning enable12(0x0C) NV Set/Get USINT OverVoltage TripThresholdOver voltage trip threshold (in percentof rated motor voltage)13(0x0D) NV Set/Get UINT Over VoltageTrip Duration Amount of time an over voltage condi-tion must exist before a trip; 0.0 - 60.0(in 0.1secs)14(0x0E) NV Set/Get USINT VoltageImbalanceTrip LevelVoltage imbalance trip threshold15(0x0F) NV Set/Get UINT VoltageImbalanceTrip DurationAmount of time a voltage imbalancecondition must exist before a trip; 0.0 -60.0 (in 0.1secs)16(0x10) NV Set/Get UINT IncomingLineFrequencyRatingExpected frequency of incoming mainsvoltage17(0x11) NV Set/Get USINT LineFrequencyTripLine frequency deviation trip enable0x00 - disable0x01 - fault enable0x02 - warning enable18(0x12)NV Set/Get USINT FrequencyDeviationTripThresholdLine frequency deviation trip threshold(in percent of rated line frequency)19(0x13) NV Set/Get UINT FrequencyTrip Duration Amount of time a frequency deviationcondition must exist before a trip; 0.0 -60.0 (in 0.1secs)20(0x14) NV Set/Get USINT PhaseReversal TripEnablePhase reversal trip enable0x00 - disable0x01 - fault enable0x02 - warning enable