146. CommissioningDual port ethernet option board installation manual MN032004EN October 2017 www.eaton.com6. CommissioningThe Eaton OPTE9 Dual Port Ethernet option board iscommissioned with the control keypad by giving values toappropriate parameters in the option board menu (or via PCtools, see Chapter 5.6 “PC Tools”).Keypad commissioning procedures and location ofparameters differ a little with different drive types:• In the SPX/SVX option board, parameters are locatedunder the menu M5 (Expander board menu)6.1 Option board menuThe control keypad makes it possible for the user to seewhich expander boards are connected to the control boardand to reach and edit the parameters associated with theexpander board.6.1.1 Option board parameters-menuThe OPTE9 board parameters are listed in the table below.All the option board parameters are saved to the optionboard (not to the control board). If the Ethernet boardis replaced by a new one, you must re-configure thenew board.Table 11. Parameters menu structure# Name Default Range Description1 Comm. Protocol Modbus TCP Modbus TCP (1),Profinet IO (2),EtherNet/IP (3)Active protocol2 IP Mode DHCP Fixed IP (1), DHCP (2) IP mode. When in DHCP mode, the IP address cannot bechanged manually.3 IP Part 1 192 1…223 IP address part 14 IP Part 2 168 0…255 IP address part 25 IP Part 3 0 0…255 IP address part 36 IP Part 4 10 0…255 IP address part 47 Subnet mask P1 255 0…255 Subnet mask part 18 Subnet mask P2 255 0…255 Subnet mask part 29 Subnet mask P3 0 0…255 Subnet mask part 310 Subnet mask P4 0 0…255 Subnet mask part 411 Default GW P1 192 0…255 Default gateway part 112 Default GW P2 168 0…255 Default gateway part 213 Default GW P3 0 0…255 Default gateway part 314 Default GW P4 1 0…255 Default gateway part 415 Comm. Timeout 10 0…65535 s Comm. Timeout16 PNIO Name of station See Chapter 6.1.7 1...240 char For profinet io only. Text is not visible in the panel.17 EIP Output instance 21 “20” (1),“21” (2),“23” (3),“25” (4),“101” (5),“111” (6),“128” (7),“131” (8)Ethernet/IP output assembly instance.18 EIP Input instance 71 “70” (1),“71” (2),“73” (3),“75” (4),“107” (5),“117” (6),“127” (7),“137” (8)Ethernet/IP input assembly instance.19 EIP Product code offset 0 0…99 Ethernet/IP product code offset. User can add valuebetween 0 and 99 to product code base value. Final productcode can be viewed from monitoring-menu