197. Modbus TCPDual port ethernet option board installation manual MN032004EN October 2017 www.eaton.com7.1.3.5 Holding registersThe values can be read with function code 3. Modbus registers are mapped to drive IDs as follows:Table 18. Defined holding registersAddress range Purpose Access type See R/W Max R/W size0001 – 2000 Eaton Application ID´s 16bit Table 19 RW 30/302001 – 2011 FBProcessDataIN 16bit Table 20 RW 11/112051 – 2070 FBProcessDataIN 32bit 1) Table 20 RW 20/202101 – 2111 FBProcessDataOUT 16bit Table 21 RO 11/02151 – 2170 FBProcessDataOUT 32bit 1) Table 21 RO 20/02200 – 10000 Eaton Application ID´s 16bit Table 19 RW 30/3010501 – 10530 IDMap 16bit Figure 28 RW 30/3010601 – 10630 IDMap Read/Write 16bit Table 22 RW 30/30 2)10701 – 10760 IDMap Read/Write 32bit 1) Table 22 RW 30/3020001 – 40000 Eaton Application ID's 32bit 1) Table 19 RW 30/3040001 – 40005 Operation day counter 16bit Table 25 RO 5/040011 – 40012 Operation day counter 32bit 1) Table 24 RO 2/040101 – 40105 Resettable operation day counter 16bit Table 27 R, Write 1 to first index to reset 5/040111 – 40112 Resettable operation day counter 32bit Table 26 RO 2/040201 – 40203 Energy counter 16bit Table 29 RO 3/040211 – 40212 Energy counter 32bit Table 28 RO 2/040301 – 40303 Resettable energy counter 16bit Table 31 R, Write 1 to first index to reset 3/040311 – 40312 Resettable energy counter 32bit Table 30 RO 2/040401 – 40430 Fault history 16bit Table 32 RO 30/040501 Communication timeout 16bit Table 34 RW 1/140511-40568 Fault history with 16 bit fault codes 16bit Table 33 RO 30/01) Not supported in current version. See chapter 5.7.1.3.5.1. Eaton application IDsApplication IDs are parameters that depend on the drive’sapplication. These parameters can be read and written bypointing the corresponding memory range directly or byusing the so-called ID map (more information below). Theeasiest way to read a single parameter value or parameterswith consecutive ID numbers is to use a straight address.It is possible to read 30 consecutive ID addresses. Noticethat the operation will fail if even one of the consecutive IDsdo not exist.Parameters which have 32 bit value can be read from theirown range. For example, if you want to read the value forID 864 (FB Status Word), the address must be set to 21726.This address value comes from values: 20000 + ((ID -1) * 2).The ID value is reduced with one because of zero-basedaddressing and the result is multiplied with 2 becauseone 32 bit value will take two (16 bit) addresses.Table 19. Parameter IDsAddressrange Purpose ID range0001-2000 16 bit application parameters 1-20002200-10000 16 bit application parameters 2200-1000020001-40000 32 bit application parameters 1-200007.1.3.5.2. FB process data inThe process data fields are used to control the drive(e.g. Run, Stop, Reference, Fault Reset) and to quickly readactual values (e.g. Output frequency, Output current, Faultcode). The values in these indexes can be read and written.The fields are structured as follows.