Commissioning10002/11 MN05006002Z-ENCreating a target configu-rationBefore the SmartWire-DT gateway can exchange data withthe PLC, it must store the found configuration of the Smart-Wire-DT slaves internally as a target configuration.X Press the “Config.” pushbutton actuator for at least twoseconds.The SmartWire-DT gateway stores the found configurationinternally as a target configuration. With the aid of thistarget configuration the SmartWire-DT coupling unit checkseach time the voltage supply is retriggered on whether thenumber and part no. of SmartWire-DT slaves present on theSmartWire-DT network are unchanged and whether theSmartWire-DT topology is functional with these.Status messages of the SmartWire-DT gateway aftercreating the target configurationTable 13: LED indication of the SmartWire-DT gateway aftercreating the target configurationFor the connected SmartWire-DT slaves the status LED fordiagnosis of the SmartWire-DT network lights up continu-ously green.h The function of the “Config.” pushbutton is disabled aslong as communication with the field bus master is active.If necessary, interrupt communication by pulling out thefield bus plug. While the SmartWire-DT coupling unit isdetermining the configuration, the SmartWire-DT LEDflashes in the colour orange, frequency (1 Hz). For theconnected SmartWire-DT slaves the status LED for diag-nosis of the SmartWire-DT network flashes in the colourgreen, frequency (1 Hz).LED StatusSWD Green continuous lightConfig. Off (no planned configuration is available)www.comoso.com