What Happens If …?11002/11 MN05006002Z-ENConfig.-LED (status project vs. target configuration)The Config. LED shows the result of the comparison of thegateway and saved target configurations, and the projectconfiguration specified by the programming system.If the configuration comparison function is disabled, the LEDis off.Table 20: Diagnostics with the Config-LEDEvent Explanation RemedyLED green contin-uous lightThe project configuration of thecontroller agrees with the target config-uration of the SmartWire-DT gateway.–LED off No communication with the field busmaster or the SmartWire-DT couplingunit does not contain a project configu-ration, e.g. after retriggering.Check the connection to the fieldbus master or transfer the projectconfiguration into the SmartWire-DT gateway.LED greenflashing (1 Hz)The target configuration does not agreewith the project configuration of thecontroller, but the parameter “Compat-ible devices allowed” has been acti-vated. The deviation allows dataexchange with the SmartWire-DT slavein question.You can find a list of the types that arecompatible with one another in themanual MN05013002Z-EN.The SmartWire-DT gateway isready for data exchange with theSmartWire-DT slaves. Check yourtarget configuration and, if neces-sary, update the project configura-tion.LED red contin-uous lightThe project configuration of thecontroller does not agree with the targetconfiguration of the SmartWire-DTgateway.The SmartWire-DT gateway is notready for data exchange with theSmartWire-DT slaves. Correct yourtarget or project configuration.www.comoso.com