SmartWire-DT network2302/11 MN05006002Z-ENSmartWire-DT station address assignmentTo operate a SmartWire-DT network, addresses must beassigned to the SmartWire-DT slaves. Addresses must beassigned during commissioning, on any changes in configu-ration and when replacing slaves. To assign addresses, pressthe Config. key on the SmartWire-DT gateway. After addressassignment, all found stations are saved in the gateway’starget configuration.The configuration state is indicated by the SmartWire-DTLED:Preconditions for address assignment:The gateway has a connection to the SmartWire-DT networkwhen its supply voltage is first switched on; the field busplug is disconnected.Pressing the Config. key for at least two seconds starts auto-matic address assignment.The SmartWire-DT gateway reports this status with thefollowing LED indication:SWD-LED StatusRed flashing No target configuration present(for initial startup)Green Target configuration presenth Pressing the Config. key when switching on the gatewaywill switch it to “Firmware update“ mode.Automatic address assignment to the SmartWire-DTslaves is not possible in this state.An operating system update can be performed with designsoftware SWD-Assist. For further information, see manualMN05013002Z-EN, “SmartWire-DT Gateway”.www.comoso.com