XI/ON: XN-1RS232 09/2011 MN05002013Z-EN www.eaton.com 392 Integrating the Module in PROFIBUS-DPFunction blocks for SIMATIC S7Table 15: Input variables of FBSRRSXXXVariable MeaningEnableRecv 1: Receiving of data enabled.0: Receiving of data disabled.EnableSend 1: Transmit data enabled.0: Transmit data disabled.Quit 1: Error messages are reset (acknowledgement of errors).Communication is stopped.0: These are retained if error messages are present.CLRBuf_Recv 1: The clearing of the receive buffer is preset. The bufferis always successfully cleared if:EnableRecv = 0Quit = 10: No influence on the module function.CLRBuf_Send 1: The clearing of the transmit buffer is preset. The bufferis always successfully cleared if:EnableSend = 0Quit = 10: No influence on the module function.RxD_K1 Start address for the 8-byte input address range of theXN-1RS232 module.The SIMATIC STEP 7 software assigns the addressranges to the appropriate modules. The address rangesare selected and displayed in the hardware configurator ofthe software.WORD format is used for the addresses and thereforeconsists of 2 bytes.Example:The decimal value 258 must be transferred in hexadecimalcode as W#16#102.