4-8 C60 Breaker Protection System GE Multilin4.2 EXTENDED ENERVISTA UR SETUP FEATURES 4 HUMAN INTERFACES45. Verify one more time that you want to remove the template by clicking Yes.The EnerVista software removes all template information and all settings are available.4.2.2 SECURING AND LOCKING FLEXLOGIC EQUATIONSThe UR allows users to secure parts or all of a FlexLogic equation, preventing unauthorized viewing or modification of criti-cal FlexLogic applications. This is accomplished using the settings template feature to lock individual entries within Flex-Logic equations.Secured FlexLogic equations remain secure when files are sent to and retrieved from any UR-series device.a) LOCKING FLEXLOGIC EQUATION ENTRIESTo lock individual entries of a FlexLogic™ equation:1. Right-click the settings file or online device and select the Template Mode > Create Template item to enable the set-tings template feature.2. If prompted, enter the template password.3. Select the FlexLogic > FlexLogic Equation Editor settings menu item.By default, all FlexLogic™ entries are specified as viewable and displayed against a yellow background. The icon onthe upper right of the window also indicates that EnerVista UR Setup is in EDIT mode.4. Specify the entries to lock by clicking on them.The locked entries display against a grey background as shown in the example.Figure 4–7: LOCKING FLEXLOGIC ENTRIES IN EDIT MODE5. Click the Save button to save and apply changes to the settings template.6. Select the Template Mode > View In Template Mode option to view the template.7. Optionally apply a password to the template by right-clicking the device and selecting the Template Mode > Pass-word Protect Template option.