5-182 C60 Breaker Protection System GE Multilin5.6 GROUPED ELEMENTS 5 SETTINGS5The C60 contains protection elements for ground time overcurrent (ANSI device 51G) and ground instantaneous overcur-rent (ANSI device 50G). A maximum of six ground time overcurrent and eight ground instantaneous overcurrent elementsare available, dependent on the CT/VT modules ordered with the relay. See the following table for details.b) GROUND TIME OVERCURRENT (ANSI 51G, IEC PTOC)PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) GROUND CURRENT GROUND TOC1(4)This element can provide a desired time-delay operating characteristic versus the applied current or be used as a simpledefinite time element. The ground current input value is the quantity measured by the ground input CT and is the funda-mental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous” (see theInverse TOC Curve Characteristics section for details). When the element is blocked, the time accumulator will resetaccording to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and the ele-ment is blocked, the time accumulator will be cleared immediately.These elements measure the current that is connected to the ground channel of a CT/VT module. The conversionrange of a standard channel is from 0.02 to 46 times the CT rating.This channel may be also equipped with a sensitive input. The conversion range of a sensitive channel is from0.002 to 4.6 times the CT rating.CT/VT MODULES GROUND CURRENT ELEMENTSSLOT F SLOT M TIMEOVERCURRENTINSTANTANEOUSOVERCURRENT8F/8G 8F/8G 4 48H/8J 6 68H/8J 8F/8G 6 68H/8J 6 8 GROUND TOC1GROUND TOC1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE GROUND TOC1 SIGNALSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE GROUND TOC1INPUT: PhasorRange: Phasor, RMSMESSAGE GROUND TOC1PICKUP: 1.000 puRange: 0.000 to 30.000 pu in steps of 0.001MESSAGE GROUND TOC1CURVE: IEEE Mod InvRange: see the Overcurrent Curve Types tableMESSAGE GROUND TOC1TD MULTIPLIER: 1.00Range: 0.00 to 600.00 in steps of 0.01MESSAGE GROUND TOC1RESET: InstantaneousRange: Instantaneous, TimedMESSAGE GROUND TOC1 BLOCK:OffRange: FlexLogic operandMESSAGE GROUND TOC1TARGET: Self-resetRange: Self-reset, Latched, DisabledMESSAGE GROUND TOC1EVENTS: DisabledRange: Disabled, EnabledNOTENOTE